Communication Manager Maintenance-Object Repair Procedures
1018 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
Table 350: Test #144 Slip Alarm Inquiry Test 
Error 
Code
Test 
Result
Description / Recommendation
ABRT
Internal system error
2100
ABRT
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals up to 5 times.
2000
ABRT
Response to the test was not received within the allowable time period. 
This may be due to hyperactivity. Error type 1538 in the error log indicates 
hyperactivity. The hyperactive circuit pack is out of service and one or more 
of the following symptoms may be exhibited.
The DS1-BD tests (such as test 138 and test 139) are aborting with 
error code 2000.
The tests run on the ports of this circuit pack are returning a no board 
result.
busyout or a release has no affect on the test results.
list config shows that the circuit pack and the ports are 
properly installed.
When hyperactivity occurs, the circuit pack is isolated from the system, and 
all of its trunks are placed into the out-of-service state. The system will try 
to restore the circuit pack within 15 minutes. When no faults are detected 
for 15 minutes, the DS1 interface circuit pack is restored to normal 
operation. Every DS1 interface trunk is then returned to the in-service 
state. Hyperactivity is often caused by the associated facility. In such a 
case, faults (such as slips, misframes, or blue alarms) would be entered in 
the error log. In addition, many hardware errors would be logged against 
the associated trunk circuits. If the facility is OK and the error occurs again 
after 15 minutes, escalate this problem.