DS1C-BD
Issue 1 June 2005
1111
 
55
FAIL
TN1654 DS1 converter packet facility is down and can’t send loop-up 
message to the far end.
1. Enter display errors and follow the associated repair procedures 
for any DS1-FAC errors on the DS1 facilities at both ends of the DS1 
converter complex. If an alarm exists on a DS1 facility, then this test will 
fail.
2. Check the DS1 connections, both circuit packs should have their DS1 
facilities connected identically.
3. Check the DS1 Converter Measurements Report to see if there are 
facilities with excessive errors. Use list measurements 
ds1-facility summary
. If there are facilities with excessive errors, 
execute the Far-End Internal Loopback test (#797) via test 
ds1-facility location
 long on those facilities, and follow repair 
procedures described for the test.
4. Both circuit packs may not have the same translation information. Run 
the Board Options Audit test (#795) via test board location 
short
 for both circuit packs in the DS1 converter complex to send the 
options. Check the results of this audit test. This test does not pass until 
the audit test problems are resolved.
PASS
DS1 facility connections are correct.
0
NO 
BOARD
The system software found no board.
1. Reset the board.
2. Remotely retry the command.
Table 377: Test #790 DS1 Facilities Connectivity Loop-Back Test  (continued)
Error 
Code
Test 
Result
Description / Recommendation