Avaya 03-300430 User Manual

Page of 2574
FIBER-LK (Fiber Link)
Issue 1 June 2005
1291
 
2306
ABRT
A fiber link’s SNI circuit pack is not responding to test requests sent by 
software.
1. Run the test led switch-node for the switch node where the SNI 
board(s) reside to verify whether their LEDs light. If not, continue with 
the following steps.
2. If LEDs light on other boards in the same carrier (but not on this 
board), enter test board location long (#760) for the active 
SNC in this carrier. Wait 5 minutes, and try step 1 again. If the board’s 
LEDs still do not light, replace the board. (Replacing an SNI may be 
service interrupting. Refer to the SNI-BD section for the procedure to 
replace an SNI.)
3. If no LEDs light on any board in the same carrier, fix any connectivity 
problems between this carrier and the media server. Use list 
fiber-link
 to list the fiber connections to this carrier. Check the 
LEDs on every SNI and EI, and fix any fiber problems. Enter display 
errors
, and resolve any SYNC, SNI-BD, SNC-BD, FIBER-LK, or 
SNI-PEER error entries.
2500
ABRT
Internal system error
1. Retry the command at 1-minute intervals up to 3 times.
141
FAIL
The SNI circuit pack (Endpoint 1 of the fiber link) has a fiber out-of-frame 
condition, but no loss-of-signal condition. Also, a lightwave transceiver is 
connected to the SNI circuit pack.
1. Check that the connected circuit pack is physically installed. The 
connected circuit pack is the other endpoint of the fiber link if no DS1 
converter complex is administered (check via list fiber-link). 
Otherwise, if a DS1 converter complex is administered, the connected 
circuit pack is the DS1 converter circuit pack connected to the SNI 
circuit pack.
2. Perform the 
 in Maintenance Procedures (03-300192) in Chapter 5.
3. Replace this SNI circuit pack.
4. Replace the connected circuit pack.
Table 443: Test #989 SNI Fiber Out of Frame Query  (continued)
Error 
Code
Test 
Result
Description / Recommendation
 3 of 9