Communication Manager Maintenance-Object Repair Procedures
336 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
Table 88: Test #78 Power Query Test 
Error
Code
Test 
Result
Description / Recommendation
1000
ABRT
System resources required to run test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
100 
2000
ABRT
Response to the test request was not received within the allowable time 
period.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the test continues to ABORT with error code 2000, check for 
system powering problems with the PN’s A carrier. Resolve every 
AC-POWER and CARR-POW (
S8700 IP
: RMC-ENV) alarm. Repeat 
the test.
3.
S8700 MC
: If the test still ABORTs with error code 2000, check for 
and resolve every MAINT (Maintenance circuit pack) error in a PN. 
Repeat the test.
4. If the test still ABORTs with error code 2000, escalate the problem.
2029 
2319 
2320 
2500
ABRT
Internal system error
1
FAIL
The cabinet is currently without AC power.
Note:
Note:
For a J58890CE, skip to 
.
Procedures for a Global MCC (J58890CH)
1. For a nominal holdover system if there is no AC power at the wall 
outlet, have a qualified electrician restore power to the outlet. Power 
should range from 170 to 264 VAC.
2. If there is AC power at the wall outlet, then there could be a problem 
with the RM0850 rectifiers, BU3200A BIU (battery interface unit), or 
battery. Resolve every alarm logged against the POWER MO, and 
rerun the test. If the test still fails, the BIU may be defective. Check 
the BIU. If the BOD alarm LED is on, replace the BIU. For 
S8700 MC
if the BOD LED is off and the BOK LED is on, then a PN’s 
Maintenance circuit pack may be incorrectly reporting the problem. 
Resolve every alarm against these MOs, and rerun the test.