Bosch ICP-CC488 User Manual

Page of 118
ICP-CC488 | Installation Guide | 8.0  
Alarm Link Software 
EN | 40 
 
 
Bosch Security Systems, Inc. | 12/08 | F01U089457-02 
 
If you are required to disable the ability restore the 
control panel to its default settings, a special 
procedure eliminates the possibility of accidentally 
setting this option. You must hold down the default 
button on the printed circuit board (PCB) when 
programming this location. 
To prevent manually restoring the default 
control panel settings: 
1.  Enter the Installer Code (the default is 1234) and 
press [#] to enter Installer’s Programming Mode. 
Two beeps sound and the remote codepad 
displays the data programmed in Location 000. 
If you are using the remote codepad, the STAY 
and AWAY indicators flash to indicate you 
entered Installer’s Programming Mode. 
2.  Enter [9 0 0 #] to move to Location 900. 
3.  Press and hold the default button.   
The default button is located at the top of the 
PCB next to the PROGRAMMING KEY socket. 
4.  Enter [1 5 *] to program 15 into Location 900. 
5.  Release the default button. 
6.  Enter [9 6 0 #] to exit from Installer’s 
Programming Mode.   
Two beeps sound and the system returns to the 
disarmed state. 
If you are using a remote codepad, the STAY 
and AWAY indicators are extinguished to 
indicate that the system is disarmed. 
If Location 900 is not programmed as 15, do one of 
the following procedures to restore the default 
control panel settings. 
To default the control panel settings using the 
Installer Code: 
1.  Enter the Installer Code (the default is 1234) and 
press [#] to enter Installer’s Programming Mode. 
Two beeps sound. The STAY and AWAY 
indicators flash to indicate you entered Installer’s 
Programming Mode. 
2.  Enter [9 6 1 #]. 
Two beeps sound after the default control panel 
settings are restored. 
3.  Enter [9 6 0 #].  
Two beeps sound. The STAY and AWAY 
indicators stop flashing and the system returns to 
the disarmed state. 
The control panel default factory settings are 
restored. 
To restore the default control panel settings using 
the default button: 
1.  Disconnect the AC MAINS supply and the 
backup battery from the control panel. 
2.  Press and hold the default button. 
The default button is located at the top of the 
PCB next to the PROGRAMMING KEY socket. 
3.  Reconnect the AC MAINS supply to the control 
panel. 
4.  Wait 3 to 5 sec and release the default button. 
5.  Enter [2 5 8 0 *] to disarm the system using the 
default Master Code. 
The control panel default factory settings are 
restored. 
 
If the option to restore the default control 
panel settings is disabled using Location 
900: 
•  The dialer seize relay (RL2) clicks 
four times. You must return the 
control panel to Bosch Security 
Systems, Inc. for exchange. If the 
Installer Code is unknown, a service 
fee is charged to unlock the control 
panel’s memory  
•  When programmed to disable the 
default control panel setting, you 
cannot use the command [961#] to 
retrieve the programming data. 
•  The use of this feature is not 
recommended. 
8.0   Alarm Link Software 
You can program or control the ICP-CC488 Control 
Panel remotely using an IBM or compatible personal 
computer and the CC816 Alarm Link Software. This 
software allows you to change your customer’s 
control panel without leaving your office, which 
improves customer service and saves you time and 
money. For locations where a control panel is 
installed hundreds of kilometers from your office, the 
Upload/Download feature is invaluable. 
When selecting the control panel type during the 
setup of a new customer database in the Alarm Link 
Software, the software version number is 
ICP-
CC488 
V1.0X and the panel type is I488. 
When you add a new customer in the Alarm Link 
Software, the Subscriber ID Number and the Installer 
Code must match the values programmed in the 
control panel for synchronization during connection 
to the control panel. If these two locations do not 
match those of the control panel, the computer and 
the control panel cannot be synchronized. 
8.1 Remote 
Connect 
The remote connect feature allows you to establish a 
connection through the telephone network from your 
IBM or compatible computer to the ICP-CC488 
Control Panel. This software allows you to offer 
faster service to your clients. 
8.1.1 
Remote Connection with Customer 
Control 
If you want to configure the control panel so that a 
remote connection can be established only when the 
client initiates it through the remote codepad, 
program the following information: