Programmable Outputs 
EN | 70 
 
 
Bosch Security Systems, Inc. | 12/08 | F01U089457-02 
 
When programming Test Report options, specify the 
hour and minute of the day the report is required, 
and how often to send the report. Test reports are 
reported on a daily basis from every day to every 
fifteen days. Refer to Section 5.1.2 Set the Number of 
Days until the First Test Report
 to set the first test 
report. 
 
If Test Reports are not required, program 
the repeat interval in Location 434 as 0. 
Program the Test Report Time as 24:00 
to send reports every 30 min. 
Example 
If you want to send Test Reports once every seven 
days at 11:35 PM, program Locations 428 to 429 as:  
[2 3 3 5 7 1 7] 
15.29  Test Reporting Dialer Options 
Location 
435 
No report allowed 
Report to Receiver 1 
Report to Receiver 2 
Report to both Receiver 1 and Receiver 2 
Report to Receiver 2 only if Receiver 1 fails 
Location 435 is set by default to report only to 
Receiver 1. You can select whether Test Reports are 
sent to Receiver 1, Receiver 2, or both, Receiver 2 
only when Receiver 1 fails, or no reporting. 
16.0  Programmable Outputs 
The ICP-CC488 Control Panel has four fully-
programmable outputs on the main printed circuit 
board and one programmable output that operates 
the codepad buzzer. The four outputs are set by 
default to operate as horn speaker, fire alarm 
verification, strobe, and internal screamer. 
Programmable outputs require four parameters to 
operate correctly. 
 
 
 
 
 
 
 
 
 
 
 
 
 
Table 54:  Output Parameters 
 
Parameter 
Description 
Event Type 
The Event Type specifies when an output 
is activated. The Output Event Types are 
listed in Section 16.2 on page 71 . Enter 
the code for the Output Event Type into 
the two corresponding locations for the 
output. 
Polarity 
Polarity determines whether the output 
operates for the duration of the event, 
pulses for the duration, operates only 
once (one shot), or latches on. The 
Polarity options are listed in Table 56 on 
page 76
Time Base/ 
Time 
Multiplier 
The Time Base and Time Multiplier 
parameters determine how long and how 
often the output operates. Refer to 
Section 16.4 Output Timing
 
Location 
436 to 465 
 
 
Location 
Default 
Output 1 (Default – Horn 
Speaker) 
 
 
Event Code 
436 
Event Code 
437 
14 
Polarity 
438 
Time Base 
439 
Time Base Multiplier 
440 
Time Base Multiplier 
441 
Output 2 (Default – Fire Alarm With Verification) 
 
Event Code 
442 
Event Code 
443 
Polarity 444 
10 
Time Base 
445 
Time Base Multiplier 
446 
Time Base Multiplier 
447 
Strobe Output (Default – Strobe – Reset After 8 hrs.) 
 
Event Code 
448 
Event Code 
449 
Polarity 450 
Time Base 
451 
Time Base Multiplier 
452 
Time Base Multiplier 
453 
Relay Output (Default – Sirens Running) 
 
Event Code 
454 
Event Code 
455 
15 
Polarity 456 
Time Base 
457 
Time Base Multiplier 
458 
Time Base Multiplier 
459 
Codepad Buzzer (Default – Entry/Exit Warning and Day 
Alarm) 
Event Code 
460 
0
Event Code 
461 
13
Polarity 462 
2
Time Base 
463 
1
Time Base Multiplier 
464 
0
Time Base Multiplier 
465 
1