Bosch ICP-CC488 User Manual

Page of 118
ICP-CC488 | Installation Guide | 15.0  
System Reporting Information 
EN | 68 
 
 
Bosch Security Systems, Inc. | 12/08 | F01U089457-02 
 
 
Restore Reports are not sent for this 
event.  
If Codepad Panic Reports are not 
required, program Locations 405 and 406 
as 0. 
15.17 Codepad Fire Report 
Location 
407 to 408 
 Location 
Default 
Tens digit 
407 
Units digit 
408 14 
A Fire Alarm Report (Contact ID Event Code 110) is 
sent to the base station receiver when a user presses 
[4] and [6] at the same time. A Fire Alarm is audible, 
but you can program the alarm as silent by selecting 
Option 2 in Location 493 (refer to Section 18.2 System 
Options 2 
on page 81). A distinct fire sound is emitted 
through the horn speaker to indicate this type of 
alarm. The fire sound is different than the burglary 
sound. 
 
Restore Reports are not sent for this 
event. 
If Codepad Fire Reports are not required, 
program Locations 407 and 408 as 0. 
15.18 Codepad Medical Report 
Location 
409 to 410 
 Location 
Default 
Tens digit 
409 
Units digit 
410 13 
A Medical Report (Contact ID Event Code 100) is 
sent to the base station receiver when a user presses 
[7] and [9] at the same time. A Medical Alarm is 
audible, but you can program the alarm as silent by 
selecting Option 4 in Location 493 (refer to Section 
18.2 System Options 2 
on page 81). 
 
Restore Reports are not sent for this 
event.  
If Codepad Medical Reports are not 
required, program Locations 409 and 410 
as 0. 
15.19  Codepad Reporting Options 
Location 
411 
No Codepad Alarm Reports allowed 
Report to Receiver 1 
Report to Receiver 2 
Report to both Receiver 1 and Receiver 2 
Report to Receiver 2 only if Receiver 1 fails 
Location 411 is set by default to report only to 
Receiver 1. You can select whether Codepad Alarm 
Reports are sent to Receiver 1, Receiver 2, or both, 
Receiver 2 only when Receiver 1 fails, or no 
reporting. 
 
15.20  System Status – AUX Power 
Supply Fail Report 
Location
412 to 413 
 Location 
Default 
Tens digit 
412 
10 
Units digit 
413 3 
A System Trouble Report (Contact ID Event Code 
300) is sent when either the codepad AUX power 
supply is blown or the AUX power supply 
malfunctions. The system reports the event 
approximately 10 sec after the failure. 
15.21  System Status – AUX Power 
Supply Fail Restore Report 
Location
414 to 415 
 Location 
Default 
Tens digit 
414 
10 
Units digit 
415 8 
A System Trouble Restore Report (Contact ID Event 
Code 300) is sent when the AUX power supply is 
reset. The system reports the event approximately 10 
sec after power supply is reset. 
15.22  System Status – AC Fail Report 
Location
416 to 417 
 Location 
Default 
Tens digit 
416 
10 
Units digit 
417 2 
An AC Fail Report (Contact ID Event Code 301) is 
sent to the base station receiver when the AC 
MAINS supply is disconnected for 2 min. If you do 
not want an AC Fail Report to be sent until the AC 
MAINS supply is disconnected for 1 hour, select 
Option 1 in Location 494 (refer to Section 18.3 System 
Options 3 
on page 81). If you want to ignore AC Fail, 
select Option 2 in Location 494. 
 
If AC Fail Reports are not required, 
program Locations 416 and 417 as 0. 
15.23  System Status – AC Fail Restore 
Report 
Location
416 to 417 
 Location 
Default 
Tens digit 
416 
10 
Units digit 
417 7 
An AC Fail Restore Report is sent when the AC 
MAINS supply is connected continuously for longer 
than 2 min.   
 
If AC Fail Restore Reports are not 
required, program Locations 418 and 419 
as 0.