ICP-CC488 | Installation Guide | 15.0  
System Reporting Information 
EN | 69 
 
 
Bosch Security Systems, Inc. | 12/08 | F01U089457-02 
 
15.24  System Status – Low Battery 
Report 
Location 
420 to 421 
 Location 
Default 
Tens digit 
420 
10 
Units digit 
421 1 
A Battery Test Failure Report (Contact ID Event 
Code 309) is sent to the base station receiver when 
the system’s battery voltage falls below 11.2 VDC or 
when a Dynamic Battery Test detects a low capacity 
battery. 
The control panel continually monitors the battery 
voltage. Refer to Section 3.13 Fault Descriptions on 
page 18 for more information. A Dynamic Battery 
Test is done every time the system is armed and 
every 4 hours after the control panel is powered up. 
 
I
f Low Battery Reports are not required, 
program Locations 420 and 421 as 0. 
15.25  System Status – Low Battery 
Restore Report 
Location 
422 to 423 
 Location 
Default 
Tens digit 
422 
10 
Units digit 
423 6 
A Low Battery Restore Report is sent if the backup 
battery is restored the next time the system is armed, 
or when the next Dynamic Battery Test reports the 
battery test is OK. 
 
If Low Battery Restore Reports are not 
required, program Locations 422 and 423 
as 0. 
15.26  System Status – Access Denied 
Location 
424 to 426 
 Location 
Default 
Code Retry Limit  
(0 = Unlimited) 
424 6 
Tens Digit 
425 7 
Units Digit 
426 12 
An Access Denied Report (Contact ID Event Code 
421) is sent to the base station receiver when the 
number of incorrect code attempts equals the 
number programmed in Location 424. An Access 
Denied Alarm is audible, but you can program the 
alarm as silent by selecting Option 8 in Location 493 
(refer to Section 18.2 System Options 2 on page 81).  
 
Restore Reports for this event are not 
transmitted.  
If Access Denied Reports are not 
required, program Locations 424 and 425 
as 0. 
Code Retries 
The Code Retries feature restricts the number of 
times an invalid User Code can be entered in an 
attempt to operate the system. Location 424 sets the 
number of incorrect code attempts that causes an 
alarm. When the number of incorrect code attempts 
equals the number programmed in this location, the 
system performs these actions: 
•  Activates the sirens, internal screamers, and 
strobes connected to the control panel. Select 
Option 8 in Location 493 (refer to Section 18.2 
System Options 2 
on page 81) to change this alarm 
to silent. 
•  Shuts down all codepads connected to the 
control panel and locks them out for the time 
period programmed in Location 478 (refer to 
Section 17.8 Codepad Lockout Time). 
•  Sends an Access Denied Report (Contact ID 
Event Code 421) to the base station receiver. 
Each time the system is armed or disarmed, the Code 
Retries counter is reset. You can program the counter 
to a value from 1 to 15. If you want the number of 
incorrect code attempts to be unlimited, program a 0 
in Location 424. In this case, the Access Denied 
Report is never generated and the system does not 
perform the three actions listed above. This function 
works when the system is armed or disarmed. 
15.27  System Status Reporting Options 
Location
427 
No report allowed 
Report to Receiver 1 
Report to Receiver 2 
Report to both Receiver 1 and Receiver 2 
Report to Receiver 2 only if Receiver 1 fails 
Location 427 is set by default to report only to 
Receiver 1. You can select whether System Status 
Reports are sent to Receiver 1, Receiver 2, or both, 
Receiver 2 only when Receiver 1 fails, or no 
reporting. 
 
15.28  Test Reporting Time 
Location
428 to 434 
 Location 
Default 
Hour of day (tens digit) 
428 
Hour of day (units digit) 
429 0 
Minute of day (tens digit) 
430 0 
Minute of day (units digit) 
431 0 
Test Report (tens digit) 
432 
Test Report (units digit) 
433 1 
Repeat interval in days 
434 
A Test Report (Contact ID Event Code 602) is a 
specific signal sent to the base station receiver and is 
normally used to test the dialing and reporting 
functions of the control panel.