Installation
16
 CAH-SVX01A-EN
TCP Base to Interior Wall 
Section Assembly (Typical)
Note: Failure to completely 
compress the gasketing may result 
in air leakage.
1
Join the two units and secure 
with field provided 5/8-inch flat 
washers and 5/8-inch X 2-1/2-inch 
grade 9 bolts though each of the 
six holes.
Figure 8. TCP base to interior wall sections
4" X 1/4"  GASKET 
SECURE 2" X 2" ANGLE TO WALL 
W/#14 S.M. SCREWS @ 12" CTR'S
INTERIOR
WALL
SPLIT
CAULK
CAULK
SPLIT
SPLIT
INTERIOR
WALL
SPLIT
BASE TO WALL ASSEMBLY COMPLETE
CAULK
2
Apply caulk the length of the 
base between the 2-inch X 2-inch 
angle on the one base section 
and the wall on the adjoining 
section. See Illustration below. 
Note: Use a polyurethane or 
equivalent caulk.
3
Secure the 2-inch X 2-inch angle 
to the adjoining wall with 
number 14 sheet-metal crews on 
12-inch centers along the length 
of the angle and wall.