Joining sections - Edge to 
Edge
Units must be installed level for 
proper drainage of condensate from 
the drain pan and for squareness of 
the sections during installation. In 
addition, each section in a multi-
section unit must be properly 
supported.
Note: Leveling each section, 
beginning with the first section, is 
critical. Failure to level and align the 
sections immediately creates greater 
misalignment or even structural 
damage afterward.
Remove all wooden blocks under 
the unit and shipping protection 
from adjoining surfaces (see 
Figure 9).
Place the first section of the air 
handler on the end of the roof 
curb or the housekeeping pad. 
The section must be level from 
side-to-side and front to back. 
Section squareness should be 
within 1/8-inch. Remove the 
bottom bolts from lifting lugs 
located at the shipping split (see 
Figure 10).
Figure 9. Remove shipping blocks
Figure 10. Remove lifting lug bolts