Trane Custom Climate Changer Air Handlers User Manual

Page of 60
Installation
18
 CAH-SVX01A-EN
Apply 1.25-inch x 0.33-inch 
ribbed butyl tape to the shipping 
split channel and shipping split 
plates (see Figure 11).
Verify the section is level prior to 
proceeding with the next section 
of the unit.
Figure 11. Apply butyl tape to shipping splits
Move the next unit section as 
close as possible from the 
previous section. The two 
sections should be close enough 
to reduce the amount of 
dragging required. This is 
particularly important when 
mounting on a roof curb to 
minimize damage to the sealant 
on the roof curb. Alignment of 
sections must be completed 
before drawing sections 
together.
Remove the bottom bolts from 
the shipping split lifting lugs (see 
Figure 12).
Figure 12. Remove bottom bolts from 
lifting lugs