Regency P48-NG2 User Manual

Page of 7
Vertical Venting with Two (2) 90° Elbows 
- Initial vertical section.
Two 45° elbows = One 90° elbow
Option
V
H
V+ V1
Maximum total pipe: length, of 
all sections, must not exceed 
30 feet.  
Total horizontal sections must 
not exceed 8 feet.
Minimum of 1 foot between 
90° elbows is required.
A)
1’ Min.
4’ Max.
2’ Min.
B)
2’ Min.
5’ Max.
3’ Min.
C)
3’ Min.
6’ Max.
4’ Min.
D)
4’ Min.
7’ Max.
5’ Min.
E)
5’ Min.
8’ Max.
6’ Min.
Vertical Venting with Two (2) 90° Elbows 
- Initial horizontal section.
Two 45° elbows = One 90° elbow
Option
H + H1
V
Maximum total pipe: length, of 
all sections, must not exceed 
30 feet.  
Total horizontal sections must 
not exceed 6 feet.
Minimum of 1 foot between 
90° elbows is required.
A)
2’ Max.
2’ Min.
B)
3’ Max.
3’ Min.
C)
4’ Max.
4’ Min.
D)
5’ Max.
5’ Min.
E)
6’ Max.
6’ Min.
Vertical Venting with Three (3) 90° 
Elbows - Initial vertical section.
Two 45° elbows = One 90° elbow
Option
V
H + H1
V+ V1
Maximum total pipe: length, of 
all sections, must not exceed 
30 feet.  
Total horizontal sections must 
not exceed 8 feet.
Minimum of 1 foot between 
90° elbows is required.
A)
2’ Min.
3’ Max.
4’ Min.
B)
3’ Min.
4’ Max.
6’ Min.
C)
4’ Min.
5’ Max.
7’ Min.
D)
5’ Min.
6’ Max.
8’ Min.
E)
6’ Min.
7’ Max.
9’ Min.
F)
7’ Min.
8’ Max.
10’ Min.
Vertical Venting with Three (3) 90° 
Elbows - Initial horizontal section.
Two 45° elbows = One 90° elbow
Option
H
V
H + H1
V+ V1
Maximum total pipe: 
length, of all sections, 
must not exceed 30 
feet.  
Total horizontal sections 
m u s t   n o t   e x c e e d   7 
feet.
Minimum of 1 foot 
between 90° elbows 
is required.
A)
1’ Max.
1’ Min.
3’ Max.
3’ Min.
B)
2’ Max.
2’ Min.
4’ Max.
5’ Min.
C)
3’ Max.
3’ Min.
5’ Max.
7’ Min.
D)
4’ Max.
4’ Min.
6’ Max.
9’ Min.
E)
5’ Max.
5’ Min.
7’ Max.
11’ Min.
P48 Gas Fireplace
65
June 2007 Regency Product Specifi cations Book
Gas Fireplaces
Gas Fir
eplaces