Regency P131-NG User Manual

Page of 40
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
19
INSTALLATION
HORIZONTAL
INSTALLATIONS
Install  the  flue  system  according  to  the
manufacturer's  instructions  included
with  the  components.
1) Set the unit in its desired location. Check to
determine if wall studs or roof rafters are in
the  way  when  the  flueing  system  is  at-
tached. If this is the case, you may want to
adjust the location of the unit. Rough in the
gas.
2) Direct Flue pipe and fittings are designed
with special twist-lock connections to con-
nect the flueing system to the appliance flue
outlet. A twist-lock appliance adaptor is an
available option that must be used in con-
junction with the Simpson Dura-Vent Direct
Vent GS system.
3) Put a bead of silicone inside the outer section
of the adapter and a bead of Mill Pac on the
inner collar. Slip the adapter over the exist-
ing inner and outer flue collar and fasten to
the  outer  collar  only  with  the  3  supplied
screws  (drilling  pilot  holes  will  make  this
easier). Level the fireplace and fasten it to
the framing using nails or screws through
the nailing strips.
4) Assemble the desired combination of pipe
and  elbows  to  the  appliance  adaptor  and
twist-lock  for  a  solid  connection.
Note:
a) Twist-lock procedure: Four indentations,
located on  the female ends of pipes and
fittings, are designed to  slide straight
onto the male ends of adjacent pipes and
fittings, by orienting the four pipe inden-
tations so they match and slide in to the
four entry slots on the male ends, Dia-
Diagram  1
b) Horizontal  runs  of  flue  must  be  sup-
ported every three feet. Wall straps are
available for this  purpose.
5) Mark the wall for a 10" x 10"  square hole.
The center of the square hole should line up
with the centerline of the horizontal pipe.
Cut and frame the 10 inch square hole in the
exterior wall where the flue will be termi-
nated. If the wall being penetrated is con-
structed of non-combustible material, i.e.
masonry block or concrete, a 7"(178mm)
dia.  (7-1/2"(191mm)  dia.  for  flex)  hole  is
acceptable.
Note: With Dura-Vent, the minimum height
is  achieved  by  installing  a  45
o
  elbow  di-
rectly  to  the  flue  adaptor.
Diagram  2
Note:
a) The horizontal run of flue must be level,
or have a 1/4 inch rise for every 1 foot
of run towards the termination. Never
allow  the  flue  to  run  downward.  This
could  cause  high  temperatures  and
may present the possibility of a fire.
b) The location of the horizontal flue termi-
nation on an exterior wall must meet all
local and national building codes, and
must not be blocked or obstructed.  For
External Flue Terminal Locations, see
diagram on page 12.
6) The  arrow  on  the  flue  cap  should  be
pointing up. Insure that the 1-1/2" clear-
ances to combustible materials are main-
tained (Diagram 3 on page 16). Install the
termination cap.
The four wood screws provided should be
replaced  with  appropriate  fasteners  for
stucco,  brick,  concrete,  or  other  types  of
sidings.
Note: If installing termination on a siding
covered  wall,  a  vinyl  siding  stand-
off  or  furring  strips  must  be  used
Note: Apply  sealant  "Mill-Pac"  to  inner
pipe  and  high  temperature  sili-
cone sealant to outer pipe on eve-
ry  twist-lock  joint.
Diagram  12
Vertical Flueing with Three (3) 90
o
 Elbows
Option
V + V1
H + H1
     A)
2'  (610mm)  Minimum
3'  (914mm)  Maximum
     B)
3'  (914mm)  Minimum
6' (1.86m) Maximum
     C)
4'  (1.22m)  Minimum
9' (2.7m) Maximum
     D)
5' (1.5m) Minimum
12' (3.6m) Maximum
gram 1. Push the pipe sections com-
pletely    together,  then  twist-lock  one
section  clockwise  approximately  one-
quarter turn, until the two sections are
fully locked. The female locking lugs will
not be visible from the outside, on the
Black  Pipe  or  fittings.  They  may  be
located by examining the inside of the
female ends.
With  the  above  options,  maximum  total  pipe  length  if  37  feet  with
minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please  note  minimum  1  foot  between  90
o
  elbows  is  required.