Quadra-Fire 7051-158B User Manual

Page of 58
Page  44
7051-158B
December 6, 2011
EDGE 60 Pellet Fireplace 
Collar 
Wire Ties
Trim Ring
Termination Cap 
3 inch Aluminum Flex 
Pipe (not included)
Figure 43.1 - Outside Air Installation
Install Outside Air Kit
•  Keep duct runs short and straight to minimize restriction. 
•  The outside air kit can be installed in three different 
locations - the left or right side or from the back of the 
fi replace.  Figure 42.1 on page 42. 
•  Locate the air inlet in a clear area, preferably into prevailing 
wind during the heating season.  Figure 42.2 on page 42.
•  Install as shown in Figure 43.1.
•  The air duct may be run vertically. 
I. Outside Air Kit Installation
Included in Kit:   2 wire ties, 1 collar assembly, 1 termina-
tion cap assembly, 1 trim ring, fasteners.  
NOTE: 
3 Inch (75mm) Aluminum Flex Pipe Not Supplied.
1.  Measure distance from fl oor to air vent opening in appli-
ance and mark location on wall.  
Use saw to cut opening in wall. 
•  Cut a 3-1/2 to 4 inches (89-102mm) opening on inside 
wall. 
*  Cut a 4 to 4-1/2 inches (102-114mm) opening on out-
side of house.
2.  Use wire tie to secure fl ex pipe to collar assembly.
3.  Slide trim ring over fl ex pipe and run pipe through wall.
4.  Attach fl ex pipe (not supplied) to outside termination 
cap with second wire tie.
5.  Secure termination cap to outside surface.
6.  Secure trim ring to the wall.
Tools Needed: Phillips Head screwdriver; wire cutters; 
hole saw or jig saw.
CAUTION! Risk of Fire or Asphyxiation! Do not draw 
outside combustion air from wall, fl oor or ceiling cavity, or 
enclosed spaces such as an attic or garage. 
 
•  Do not place outside air inlet close to exhaust vents 
or chimneys. 
Fumes or odors could be drawn into the 
room.
 
 
•  Locate outside air inlet to prevent blockage from 
leaves, snow/ice, or other debris. 
Blockages could 
cause combustion air starvation.
Outside air is required on ALL installations.  The Out-
side Air Kit must be ordered seperately.