Quadra-Fire 7051-158B User Manual

Page of 58
Page  46
7051-158B
December 6, 2011
EDGE 60 Pellet Fireplace 
L.  Through the Wall
Figure 45.1
12 in.
(305mm)
Minimum 
W all 
Thimble 
Horizontal 
T ermination 
Cap 
6 in.
(152mm)
Minimum
From Glass
Non-combustible 
Hearth Extension
0 in. (0mm) to Standoff
Straight Out
Wall  
Thimble 
Illustration shows venting going in both directions.  
Choose which one is best for your installation.
1-1/6 in.( 27mm)
Minimum
1-16 in. 
(27mm)
Minimum
12 in. (305mm) 
Minimum
12 in. (305mm) 
Minimum
Figure 45.2
45 Degree
Horizontal termination cap must be a minimum of 12 inches 
(305mm) from the wall.  Approved for mobile home installations.  
Must use 3 or 4 inch (76mm-102mm) “L” or “PL” Listed pellet 
venting and a Quadra-Fire Outside Air Kit in ALL installations.
NOTE:
In Canada, where passage through a wall or partition of 
combustible construction is desired, the installation shall 
conform to CAN/CSA-B365
NOTICE!  See Section 8 “Avoiding Smoke and Odors” to minimize soot 
damage to exterior walls of the house and to prevent re-entry of soot or ash 
into the house for horizontal vent confi guration