A  discharge  pipe  from  the  relief  valve  should  terminate  at  an 
adequate floor drain.  Do  not  thread,  plug,  or  cap  the  end  of 
drain line.
The Discharge Pipe:
•  Shall not be smaller in size than the outlet pipe size of the 
valve, or have any reducing couplings or other restrictions.
•  Shall not be plugged or blocked.
•  Shall not be exposed to freezing temperatures.
•  Shall be of material listed for hot water distribution.
•  Shall be installed so as to allow complete drainage of both 
the relief valve and the discharge pipe.
•  Must terminate a maximum of six inches above a floor 
drain or external to the building. In cold climates, it is 
recommended that the discharge pipe be terminated at an 
adequate drain inside the building.
•  Shall not have any valve or other obstruction between the 
relief valve and the drain.
Once the boiler is installed and filled with water and the system 
is pressurized, manually test the operation of the pressure relief 
valve. See the Maintenance Procedures section of this manual 
for instructions.
Your  local  code  authority  may  have  other  specific  safety  relief 
valve  requirements  not  covered  below.  If  any  pressure  relief 
valve is re placed, the replace ment valve must com ply with the 
current version of the ASME Boiler and Pressure Vessel Code, 
Section IV (“HEATING BOILERS”).
XB HYDRONIC BOILERS, are shipped with a 50 psi (345 kPa) 
pressure  relief  valve. This  relief  valve  must  be  in stalled  in  the 
water outlet as near to the boiler as possi ble.
XW HOT WATER BOILERS, are shipped with a 125 psi (860 
kPa) pressure relief valve that must be in stalled in the water out-
let as near to the boil er as possi ble.
This ASME-rated valve has a discharge capacity that exceeds 
maximum boiler input rating and a pres sure rating that does not 
exceed maxi mum working pres sure shown on boiler rating plate. 
In addition, a CSA design-certified and ASME-rated tempera ture 
and pressure (T&P) relief valve must be installed on each and 
every water storage tank in hot water supply system. The T&P 
relief valve must comply with appli cable construction provisions 
of Standard for Relief Valves for Hot Water Supply Systems, ANSI 
Z21.22 or CSA 4.4. T&P re lief valve must be of automatic reset 
type and not embody a single-use type fusible plug, cartridge or 
linkage.
T&P  relief  valve  should  have  a  temperature  rating  of  210°F 
(99°C),  a  pressure  rating  not  exceeding  lowest  rated  working 
pressure  of  any  system  compo nent,  and  a  discharge  capacity 
exceeding total input of water boilers supply ing water to storage 
tank.
Locate the T&P relief valve (a) in the top of the tank, or (b) in 
the  side  of  the  tank  on  a  centerline  within  the  upper  6  inches 
(152 mm) of the top of the tank, see Figure 78 and Figure 79. 
The tapping should be threaded in accordance with the current 
edition  of  the  Standard  for  Pipe  Threads,  General  Purpose 
(inch), ANSI/A SME B1.20.1. The location of, or in tended location 
for, the T&P relief valve should be readily accessible for servicing 
or replacement.
GAS CONNECTIONS
Make sure the gas on which boiler is to operate is same as that 
specified on the rating plate. Do not install boiler if equipped for a 
different type of gas. Consult your gas supplier.
This  boiler  is  not  intended  to  operate  at  gas  supply  pressure 
other than shown on the rating plate.  A lock-up or positive shut-
off type regulator must be installed in gas supply line. For proper 
gas regulation the lock-up style regulators must be installed no 
closer than a minimum of 3 feet from the boiler and a maximum 
of  8  feet  away  from  the  boiler.  Exposure  to  higher  gas  supply 
pressure may cause damage to gas valves which can result in 
fire or explosion. If overpressure has occurred such as through 
improper testing of gas lines or emergency malfunction of supply 
system,  the  gas  valves  must  be  checked  for  safe  operation. 
Make sure that the outside vents on supply regulators and the 
safety  vent  valves  are  protected  against  blockage.  These  are 
parts of the gas supply system, not boiler. Vent blockage may 
occur during ice build-up or snowstorms.
The boiler must be isolated from the gas supply piping system by 
closing its main manual gas shut off valve during any pressure 
testing of the gas supply  piping system at test pressures equal 
to or less than 1/2 psig.
Disconnect  the  boiler  and  its  main  manual  gas  shut-off  valve 
from  the  gas  supply  piping  during  any  pressure  testing  of  the 
gas supply system over 1/2 psig.  The gas supply line must be 
capped when not connected to the boiler.
CAUTION
• 
Pressure Relief Valve discharge pipe must 
  terminate at adequate drain.
Water Damage Hazard
Explosion Hazard
Relief Valve must comply with 
ASME code.
Properly sized Relief Valve must
be installed in opening provided.
Can result in overheating and
excessive tank pressure.
Can cause serious injury or death.