Configuring System for Stacked Operation
Verify all DC and AC connections. Check Xanbus network 
connections and ensure that terminators are installed at devices at 
each end of the network. The simplest system includes a Xanbus 
SCP, the two Freedom SW 230V inverter/chargers to be stacked and 
two Xanbus terminators. 
For both units to operate in stacked configurations, a Master and 
Slave have to be assigned. The default out-of-box configuration for 
all Freedom SW 230V inverter/chargers is Master which causes a 
conflict the first time the system is powered up. The installer will 
need to change configuration on one of the inverter/chargers to 
Slave mode. 
To configure the system for stacking:
1.
Apply DC power to both inverter/chargers.
Power up order has no impact. Because there are now two 
Master units in the system, the SCP will display an F66 fault, a 
“system configuration fault”. 
2.
From the SCP System Status screen, press Enter. The 
Select Device screen appears.
3.
Select the inverter to configure as a Slave unit from the list, 
then press Enter.
4.
Bring up the Advanced Settings screen by pressing Enter
Up, and Down arrow buttons all together.
5.
Select Advanced Settings and press Enter. The Advanced 
Settings screen appears.
6.
Scroll down to select Stacking
At this point all devices in the system will be automatically 
placed in standby mode. All three LEDs on the inverter to be 
configured will start flashing.
7.
Select Stack Mode and press Enter.
8.
For Parallel Stacking: Select Slave and press Enter.
9.
Press the Func button repeatedly until the System Status 
screen appears.
NOTES:
The only situation in which the Slave may shut down the Master 
inverter is during fault conditions such as high or low battery 
voltage, overcurrent, or over-temperature conditions. Both inverters 
will auto reset after a fault condition has been cleared. The 
exception is that an overcurrent condition will generate a shutdown 
for both inverters that will require a manual restart of the system.
Figure 19 Stacking Menu Screen
FSW3524 00: Stacking
Dev Name
Dev Number
Stack Mode
Battery
[00]
[01]
[Master]
[Batt1]
[*Master] [Slave] [L2Master]  
Freedom SW 3K2K 230V InvChg Install Guide.book  Page 45  Friday, June 20, 2014  9:11 AM