Stacking Features
Search Mode Operation in Parallel 
Stacking
When two inverter/chargers are stacked for parallel operation, 
search mode behavior on the Slave unit is modified and is 
dependent on how much total load is on the system.
Disabling Search Mode on the Master Unit
In parallel stacking, search mode on the Master unit will not 
function properly. When the Master sends out a load search pulse, a 
small current also flows into the output of the Slave unit since the 
two outputs are in parallel. This Master unit falsely detects a load 
causing erratic search mode operation. For this reason, it is highly 
recommended to disable search mode on the Master unit in a 
parallel stacking system.
Setting Search Mode on the Slave Unit
The Slave unit will behave in one of two ways depending on 
whether its search mode is enabled or disabled.
Search mode enabled
This is the recommended mode for parallel 
stacking and it helps minimize battery draw. The Slave unit 
continuously monitors the output of the Master unit. If the Master 
unit has more than 60% of the rated load (for example, 2100 watts 
on Freedom SW 3524-230), the Slave unit will assist the Master and 
the two will share the load equally. Should the load on the Master 
drop below 20% of rated load (700 watts for Freedom SW 3524-
230), the Slave unit disengages and returns to a waiting state.
Search mode disabled
The Slave unit operates continuously 
along with the Master unit and shares the load.
Wiring Schematic
NOTE: Please refer to the Stacking Configuration sheet that shows 
the wiring schematic employed between two Freedom SW 230V 
inverter/chargers that are stacked in parallel.
IMPORTANT: Follow the same guidelines in “Installing the 
Inverter/Charger” on page 17 
when choosing cables and/or wires for 
AC and DC connections.
FIRE, ELECTRICAL SHOCK, AND ENERGY HAZARDS
Make sure all wiring being used to make stacking configurations between 
inverter/chargers is disconnected (physically or by opening the breaker) 
from all electrical sources before handling. All wiring must be done in 
accordance with local and national electrical wiring codes.
Failure to follow these instructions will result in death or serious 
injury.