Delta Electronics DVPCOPM-SL User Manual
CANopen Communication Module DVPCOPM-SL
DVP-PLC Application Manual
6
3. POWER, RUN, ERR indicators
8. Function switch
4. DIN rail clip
9. CANopen connection port
5. Digital display
2.3 CANopen
Connection
Port
The connector is used on the connection to CANopen network. Wire by using the connector enclosed with
DVPCOPM-SL.
PIN
Signal
Content
1 GND
0
VDC
2 CAN_L
Signal-
3 SHLD
Shielded
4 CAN_H
Signal+
5 -
Reserved
4
GND
SHLD
CAN-
CAN+
5
3
2
2
1
2.4 Address
Switch
The switch is used on setting up the node address of DVPCOPM-SL on CANopen network. Range: 1 ~ 7F (0,
88 ~ FF are forbidden).
Switch setting
Content
1 ~ 7F
Valid CANopen node address
0, 80 ~ FF
Invalid CANopen node address
NO
DE
A
D
D
R
E
S
S
x16
0
x16
1
Example: If you need to set the node address of DVPCOPM-SL to 26 (1AH), simply switch the corresponding
switch of x16
1
to 1 and the corresponding switch of x16
0
to A.
Note:
z Use slotted screwdriver to rotate the switch carefully in case you scratch the switch.
z Please set up the node address when the power is switched off. After the setup is completed, re-poser
DVPCOPM-SL.
2.5 Function
Switch
The switch is used on setting up the baud rate between DVPCOPM-SL and CANopen network (DR0 ~ DR2).
See the table below for the baud rate and its maximum communication distance.
DR2
DR1
DR0
Baud rate (bps)
Max. communication distance (m)
OFF OFF OFF
10k
5,000
OFF OFF ON
20k
2,500
OFF ON OFF
50k
1,000
OFF ON ON
125k
500
ON OFF OFF
250k
250
ON OFF ON
500k
100
ON ON OFF
800k
50
ON ON ON
1M
25
IN0 Reserved