Chapter 2 Installation and Wiring|VFD-S Series 
2-24 
 Revision August 2006, SE08, SW V2.61
2.4.4 Control Terminals 
Control Terminal Wiring (Factory Setting) 
A. XXXSXXA/B/D/U 
RA
M1
AVI
10V
+
AFM M0
M4
M2 M3
M5
GND
RB
RC
MO1
MCM
RJ11
Multi-step speed 3
Multi-step speed 2
Multi-step speed 1
Reset
Reverse/Stop
Forward/Stop
Corrector
potentiometer
VR : 1K~5K
Freq. meter
0~10 VDC
Full scale voltmeter
Operation freq.
setting
potentiometer
VR : 3K~5K
Relay contactor output
Factory setting : Fault indication
Photo coupler output
Factory setting : in work
6 ~ 1
RS485 Communication port
 
 
B. XXXSXXE 
Multi-step speed 3
*
*
 
 
 
Terminal symbols and functions 
Terminal 
Symbol 
Terminal Function 
Factory Settings (NPN mode) 
ON: Connect to GND 
M0 
Multi-function auxiliary input 
M1 
Multi-function input 1 
M2 
Multi-function input 2 
M3 
Multi-function input 3 
Refer to Pr.4-04 to Pr.4-08 for programming the 
Multi-function Inputs. 
ON:  the activation current is 16mA.  
OFF:  leakage current tolerance is 10μA. 
Wire Gauge: 24-12 AWG 
Wire Type: Copper Only 
Torque: 4 kgf-cm (3.5 in-lbf)
Wire Gauge: 24-16 AWG 
Wire Type: Copper Only 
Torque: 2 kgf-cm (1.7 in-lbf)