Delta Electronics VFD007S23A User Manual

Page of 186
Chapter 2 Installation and Wiring|VFD-S Series 
2-26 
 Revision August 2006, SE08, SW V2.61
Terminal 
Symbol 
Terminal Function 
Factory Settings (NPN mode) 
ON: Connect to GND 
AVI 
Analog voltage Input 
(AVI/ACI) 
 
 
0~+10V/4-20mA corresponds to 0-max. 
operation frequency (Pr.01-00) 
 
PID feedback signal 
AVI input impedance: 100kohm 
ACI input impedance: 250kohm 
GND
AVI
+10V
Internal Circuit
AVI circuit
AVI
J1
ACI
 
GND
ACI
Internal Circuit
ACI circuit
AVI
J1
ACI
 
Control signal wiring size: 18 AWG (0.75 mm
2
) with shielded wire. 
 
Analog input terminals (AVI, GND) 
  Analog input signals are easily affected by external noise. Use shielded wiring and keep 
it as short as possible (<20m) with proper grounding. If the noise is inductive, connecting 
the shield to terminal GND can bring improvement. 
  If the analog input signals are affected by noise from the AC motor drive, please connect 
a capacitor (0.1
μ
F and above) and ferrite core as indicated in the following diagrams: 
C
AVI
GND
ferrite core
 
wind each wires 3 times or more around the core 
Digital inputs (M0~M5, GND) 
  When using contacts or switches to control the digital inputs, please use high quality 
components to avoid contact bounce.