Chapter 5 Parameters|VFD-S Series 
Revision August 2008, SE09, SW V2.61 
5-77
 
 
This parameter selects the operation of the drive upon a loss of PID feedback signal. 
 
A-10 
Sleep Frequency 
Unit: 0.1
 
Settings 
d0.0 to d400Hz 
Factory Setting: d0.0
 
A-11 
Wakeup Frequency 
Unit: 0.1
 
Settings 
d0.0 to d400Hz 
Factory Setting: d0.0
 
A-12 
Sleep Period 
Unit: 0.1
 
Settings 
d0.0 to d650 seconds 
Factory Setting: d0.0
 
 These parameters determine sleep functions of the AC drive.  If the command frequency falls 
below the sleep frequency, for the specified time in Pr. A-12, then the drive will shut off the 
output and wait until the command frequency rises above Pr. A-11.  Please see the below 
diagram. 
 
A-11
A-10
A-12
0Hz
Sleep  Function
Sleep Period
Sleep Frequency
Wakeup Frequency
Frequency Command
Actual running
output frequency
 
 
A-13 
PID User Defined 
Unit: 0.1
 
Settings 
d0.0 to d400 
Factory Setting: d0.0
 
 When parameter A-13 is set to 0, what F and H display is the actual value of setting 
frequency and output frequency. When this parameter is not set to 0, the display value of F 
and H = actual value ¯A-13/1-00. To set frequency with panel, communication, VR, AVI or 
ACI need to set according to the display value. For example, when 1-00=60.0Hz, if A-13 is set 
to 30.0 Hz, it means when the actual value of frequency is 30.00 Hz, the display value will be 
15.0 Hz . If you want to let drive run at 10.0Hz, the frequency command must be 5.0 Hz. But