Raritan Computer EMX2-111 User Manual

Page of 379
Chapter 7: Event Rules, Event Actions and Application Logs 
 
154
 
 
 
Event/Context 
Default Assertion Message when 
the Event = TRUE 
Default Assertion Message 
when the Event = FALSE* 
Power Logic Device > * > 
Sensor > * > Below lower 
critical threshold 
Sensor '[PLSENSORNAME]' on Power 
Logic Device at [PORTTYPE] port 
'[PORTID]' asserted 'below lower 
critical' at [SENSORREADING] 
[SENSORREADINGUNIT]. 
Sensor '[PLSENSORNAME]' on 
Power Logic Device at 
[PORTTYPE] port '[PORTID]' 
deasserted 'below lower critical' at 
[SENSORREADING] 
[SENSORREADINGUNIT].")) 
User Activity > * > User 
accepted the Restricted Service 
Agreement 
User '[USERNAME]' from host 
'[USERIP]' accepted the Restricted 
Service Agreement. 
User '[USERNAME]' from host 
'[USERIP]' declined the Restricted 
Service Agreement. 
*Note: Not set for 'trigger' events (see [ASSERTION] ctx) 
 
Sample Event Rules 
Sample Asset-Management-Level Event Rule 
In this example, we want the EMX to record in the internal log when an 
asset sensor network link goes up or down. The sample event rule looks 
like this:  
 
Event: Device > Network interface link state is up 
 
Trigger condition: Both 
 
Actions: System Event Log Action 
 
To create the above event rule: 
1.  Enter a name for the rule. 
2.  Select the Enabled checkbox to enable the rule. 
3.  From the Event drop-down, select Device > "Network interface link 
state is up". These selections indicate we are specifying an event 
regarding asset sensor management, and we want the EMX to 
respond to the event related to physical connections and/or 
disconnections. 
4.  Select the Both radio button since we want both connection and 
disconnection actions to be recorded when either action is taken.