Raritan Computer EMX2-111 User Manual

Page of 379
 
Chapter 7: Event Rules, Event Actions and Application Logs 
 
 
155
 
 
5.  Select "System Event Log Action" as we intend to record this event 
in the internal log when the specified events occur. 
 
 
Sample Sensor-Level Event Rule 
In this example, we want the EMX device to send SNMP traps to the 
SNMP manager when the reading of the temperature sensor connected 
to the sensor port #1 crosses any threshold or when the sensor is 
unavailable. To do that we would set up an event rule like this: 
 
Event: External sensor slot > Slot 1 > Numeric Sensor > Any sub-
event 
 
Actions: System SNMP Trap Action 
 
To create the above event rule: 
1.  Select "External sensor slot" in the Event field to indicate we are 
specifying an event at the environmental sensor level. 
2.  Select "Slot 1" from the submenu because we want the report about 
the sensor connected to sensor port #1. 
3.  Select "Numeric Sensor" to indicate the sensor is a numeric sensor. 
Note: A numeric sensor uses numeric values to indicate the 
environmental condition while a discrete (on/off) sensor uses 
alphabetical characters to indicate the sensor state.