Schneider Electric 61 User Manual

Page of 131
89
Output value parameters
Output values (motor)
Code
Description
LCr
Parameter name:
Motor current
Terminal display:
[Motor current]
Logic address:
3204 = 16#0C84
Type:
UINT
CANopen index:
2002/5
Read/write:
R
INTERBUS index:
5FB9/06
Unit:
0.1 A
DeviceNet path:
2A/01/09 (1)
71/01/05 (2)
Parameter conforming to ODVA profile
UOP
Parameter name:
Motor voltage
Terminal display:
[Motor voltage]
Logic address:
3208 = 16#0C88
Type:
UINT
CANopen index:
2002/9
Read/write:
R
INTERBUS index:
5FB9/0A
Unit:
1 V
DeviceNet path:
71/01/09
OPr
Parameter name:
Motor power
Terminal display:
[Motor power]
Logic address:
3211 = 16#0C8B
Type:
INT
CANopen index:
2002/C
Read/write:
R
INTERBUS index:
5FB9/0C
Unit:
1%
DeviceNet path:
71/01/0C
UNT
Parameter name:
Units of parameters APH, PTH, RTH and RTHI
Logic address:
3234 = 16#0CA2
Type:
WORD (bit register)
CANopen index:
2002/23
Read/write:
R
INTERBUS index:
5FB9/18
DeviceNet path:
71/01/23
The unit changes automatically when the value reaches the maximum format of the parameter.
bit 0 + bit 1 = unit of APH: 0 = Wh, 1 = kWh, 2 = MWh
bit 2 + bit 3 = unit of PTH: 0 = seconds, 1 = minutes, 2 = hours
bit 4 + bit 5 = unit of RTH: 0 = seconds, 1 = minutes, 2 = hours
bit 6 + bit 7 = unit of RTHI: 0 = seconds, 1 = minutes, 2 = hours
bit 8 + bit 9 =
unit of IPHR: 0 = Wh, 1 = kWh, 2 = MWh
bit 10 + bit 11 =
unit of IPH: 0 = Wh, 1 = kWh, 2 = MWh
bits 12 to 15:
Reserved (= 0)
(1)  ODVA standard path. It can be used for explicit messaging. Do not use it for configuring an assembly.
(2)  Altivar path. To ensure better interchangeability, avoid using it for explicit messaging. This is the path that must be used for configuring 
an assembly.