Schneider Electric 61 User Manual

Page of 131
90
Reference parameters
 
References (speed)
Code
Description
FrHd
Parameter name:
Speed reference before ramp
Logic address:
8605 = 16#219D
Type:
INT
CANopen index:
2038/6
Read/write:
R
INTERBUS index:
6043/0
Unit:
rpm
DeviceNet path:
8C/01/06
FrOd
Parameter name:
Speed reference after ramp
Terminal display:
CiA402 name:
vl velocity demand
DRIVECOM name:
Speed-Reference-Variable
Logic address:
8641 = 16#21C1
Type:
INT
CANopen index:
6043/0
Read/write:
R
INTERBUS index:
5FB9/DB
Unit:
rpm
DeviceNet path:
8C/01/2A
Parameter conforming to CiA402 profile
Signed value.
This parameter is linked to the "Frequency after ramp" 
(FRO)
 parameter for which the unit is 0.1 Hz.
FrH
Parameter name:
Frequency reference before ramp
Terminal display:
[Frequency ref.]
Logic address:
3203 = 16#0C83
Type:
INT
CANopen index:
2002/4
Read/write:
R
INTERBUS index:
5FB9/05
Unit:
0.1 Hz
DeviceNet path:
71/01/04
FrO
Parameter name:
Frequency reference after ramp
Logic address:
9021 = 16#233D
Type:
INT
CANopen index:
203C/16
Read/write:
R
INTERBUS index:
5FB9/DC
Unit:
0.1 Hz
DeviceNet path:
8E/01/16