I/O parameters
 
98
Analog outputs
The analog outputs can be controlled via the network. Simply write these parameters. The outputs to be controlled must not be assigned 
to a drive function, otherwise the write operation has no effect. 
Code
Description
AI4C
Parameter name:
Physical image of analog input 4
Logic address:
5245 = 16#147D
Type:
INT
CANopen index:
2016/2E
Read/write:
R
INTERBUS index:
5FB9/39
Unit:
0.001 V or 0.001 mA
DeviceNet path:
7B/01/2E
The unit is:
• 0.001 V if parameter 
[AI4 Type]
 
(AI4t)
 is configured as 
[Voltage]
 
(10U)
• 0.001 mA if parameter 
[AI4 Type]
 
(AI4t)
 is configured as 
[Current]
 
(0A)
AI4r
Parameter name:
Standardized image of analog input 4
Logic address:
5235 = 16#1473
Type:
INT
CANopen index:
2016/24
Read/write:
R
INTERBUS index:
5FB9/35
Unit:
1
DeviceNet path:
7B/01/24
Code
Description
AO1C
Parameter name:
Physical image of analog output 1
Logic address:
5271 = 16#1497
Type:
INT
CANopen index:
2016/48
Read/write:
R/W
INTERBUS index:
5FB9/40 (reading via PCP)
5FB6/50 (writing via PCP)
Unit:
0.001 mA or 0.001 V
DeviceNet path:
7B/01/48
The unit is:
• 0.001 V if parameter 
[AO1 Type]
 
(AO1t)
 is configured as 
[Voltage]
 
(10U)
• 0.001 mA if parameter 
[AO1 Type]
 
(AO1t)
 is configured as 
[Current]
 
(0A)
AO1r
Parameter name:
Standardized image of analog output 1
Logic address:
5261 = 16#148D
Type:
INT
CANopen index:
2016/3E
Read/write:
R/W
INTERBUS index:
5FB9/3D (reading via PCP)
5FB6/4F (writing via PCP)
Unit:
1
DeviceNet path:
7B/01/3E
AO2C
Parameter name:
Physical image of analog output 2
Logic address:
5272 = 16#1498
Type:
INT
CANopen index:
2016/49
Read/write:
R/W
INTERBUS index:
5FB9/41 (reading via PCP)
5FB6/52 (writing via PCP)
Unit:
0.001 mA or 0.001 V
DeviceNet path:
7B/01/49
The unit is:
• 0.001 V if parameter 
[AO2 Type]
 
(AO2t)
 is configured as 
[Voltage]
 
(10U)
 or 
[Voltage +/-]
 
(n10U)
• 0.001 mA if parameter 
[AO2 Type]
 
(AO2t)
 is configured as 
[Current]
 
(0A)