Schneider Electric 61 User Manual

Page of 131
99
I/O parameters
 
Encoder
Code
Description
AO2r
Parameter name:
Standardized image of analog output 2
Logic address:
5262 = 16#148E
Type:
INT
CANopen index:
2016/3F
Read/write:
R/W
INTERBUS index:
5FB9/3E (reading via PCP)
5FB6/51 (writing via PCP)
Unit:
1
DeviceNet path:
7B/01/3F
AO3C
Parameter name:
Physical image of analog output 3
Logic address:
5273 = 16#1499
Type:
INT
CANopen index:
2016/4A
Read/write:
R/W
INTERBUS index:
5FB9/42 (reading via PCP)
5FB6/54 (writing via PCP)
Unit:
0.001 mA or 0.001 V
DeviceNet path:
7B/01/4A
The unit is:
• 0.001 V if parameter 
[AO3 Type]
 
(AO3t)
 is configured as 
[Voltage]
 
(10U)
 or 
[Voltage +/-]
 
(n10U)
• 0.001 mA if parameter 
[AO3 Type]
 
(AO3t)
 is configured as 
[Current]
 
(0A)
AO3r
Parameter name:
Standardized image of analog output 3
Logic address:
5263 = 16#148F
Type:
INT
CANopen index:
2016/40
Read/write:
R/W
INTERBUS index:
5FB9/3F (reading via PCP)
5FB6/53 (writing via PCP)
Unit:
1
DeviceNet path:
7B/01/40
Code
Description
PUC
Parameter name:
Pulse counter
Logic address:
5611 = 16#15EB
Type:
UINT
CANopen index:
201A/C
Read/write:
R
INTERBUS index:
5FB9/44
Unit:
1
DeviceNet path:
7D/01/0C