Sanyo E11A202U User Manual

Page of 47
 
− 23 − 
 
 
 
 
10. User Settings 
 
10.1 Setup Menu Item List 
You can configure the UPS by setting the menu items in the following list. 
Configure it according to your environment and requirements.   
The controls and indicators on the control panel are used to set items in the Setup 
menu. For details, see §10.2 “Setup Menu Operations”. 
Whenever you change a menu item setting, we recommend that you place a check 
mark in the “Current Setting” field of the Setup Menu Item List. 
 
No.  Menu Item 
Item Selection 
LEDs 
Setting 
Item Setting 
LEDs 
Default 
Setting 
Current 
Setting 
Description 
 Notes 
Auto 
● ○ ○ ○
 
 
Switch the UPS operating mode automatically. 
Double Conversion  ○ ● ○ ○  
 
 
Set the UPS operating mode to Double Conversion mode. 
 
UPS operation mode 
 
● ○ ○ ○
 
Economy 
● ● ○ ○
 
 
 
Set the UPS operating mode to Economy mode. 
However, the mode of UPS might change into the “Double Conversion” 
mode depending on the condition of the input potential and the load. 
100V 
● ○ ○ ○
 
 
 
100V setting 
110V 
○ ● ○ ○
 
 
 
110V setting 
115V 
● ● ○ ○
 
 
 
115V setting 
 
Output voltage 
(RESTART) 
 
○ ● ○ ○
 
120V 
○ ○ ● ○
 
 
120V setting 
Set the rated output voltage. 
The case of E11A202U001 
Please do not change setting the voltage. 
And use UPS as 120V setting.   
(For UL rules) 
1% 
● ○ ○ ○
 
 
 
±1% allowance 
3% 
○ ● ○ ○
 
 
±3% allowance 
 
Frequency sync range 
(RESTART) 
 
● ● ○ ○
 
5% 
● ● ○ ○
 
 
 
±5% allowance 
Set the range (%) over which the output 
frequency is adjusted to variations in the 
input frequency in Economy Mode and 
Active Filter Mode. 
50Hz 
● ○ ○ ○
 
 
 
50Hz setting 
 
Battery startup 
frequency 
 
○ ○ ● ○
 
60Hz 
○ ● ○ ○
 
 
60Hz setting 
Set the inverter output frequency when 
UPS restarts from the batteries from 
stopped status. 
Do not use this setting. 
● ○ ○ ○
 
 
 
 
Workstation 
○ ● ○ ○
 
 
Setting for communications by the power management software over serial 
or LAN connection. 
Serial Login 
● ● ○ ○
 
 
 
Shutdown by serial login. 
 
PC Interface mode 
 
● ○ ● ○
 
Do not use this setting. 
○ ○ ● ○
 
 
 
 
9600 
● ○ ○ ○
 
 
Set the baud rate to 9600 bps. 
4800 
○ ● ○ ○
 
 
 
Set the baud rate to 4800 bps. 
 
Serial baud rate 
 
○ ● ● ○
 
2400 
● ● ○ ○
 
 
 
Set the baud rate to 2400 bps. 
Set the communications baud rate when 
a workstation, PC, or optional LAN card 
is connected. 
Auto 
● ○ ○ ○
 
 
Auto restart 
OFF 
○ ● ○ ○
 
 
 
The UPS stays off. 
30% 
● ● ○ ○
 
 
 
Same behavior as Auto when 
battery charge reaches 30%. 
50% 
○ ○ ● ○
 
 
 
Same behavior as Auto when 
battery charge reaches 50%. 
 
Restart time 
(battery charge rate) 
 
● ● ● ○
 
80% 
● ○ ● ○
 
 
 
Same behavior as Auto when 
battery charge reaches 80%. 
Specify when to restart the UPS after a 
power outage and shutdown of the UPS 
due to final discharge of the batteries.   
When 30%, 50%, or 80% is selected, the 
UPS does not restart until the batteries 
are charged to the specified level. 
All patterns 
● ○ ○ ○
 
 
All sounds 
Patterns 1 
○ ● ○ ○
 
 
 
Do not emit sounds on power outage, battery test, and overload. 
Pattern 2 
● ● ○ ○
 
 
 
Emit alarm and key click sounds. 
 
Buzzer sound 
 
○ ○ ○ ●
 
OFF 
○ ○ ● ○
 
 
 
Emit key click sounds only. 
1 second 
● ○ ○ ○
 
 
Turn inverter off when pressed for 1 second. 
3 seconds 
○ ● ○ ○
 
 
 
Turn inverter off when pressed for 3 seconds. 
Set the response time for 
switch press to stop inverter 
power supply. 
 
  switch 
 response time 
 
● ○ ○ ●
 
Special operation 
● ● ○ ○
 
 
 
Turn inverter off on special operation. Select this setting to keep the 
inverter from being turned off by an accidental operation. See §9.4 "UPS 
Shutdown (Daily)" for operation details. 
Auto return 
● ○ ○ ○
 
 
Auto recovery with time 
 
Overload recovery 
operation 
 
○ ● ○ ●
 
Bypass 
○ ● ○ ○
 
 
 
Fixed as bypass on overload 
Set the conditions for automatic switch 
back to inverter power supply (auto 
return) after switching to bypass power 
supply because of overload. 
OFF 
● ○ ○ ○
 
 
The UPS stays off. 
 
Inverter stop 
Operation (RESTART) 
 
● ● ○ ●
 
Bypass 
○ ● ○ ○
 
 
 
Switch to bypass operation when 
inverter stops. 
Specify the UPS operation during 
inverter power supply stops. 
Battery voltage level 
● ○ ○ ○
 
 
When low battery voltage level is 
detected. 
2 minutes 
○ ● ○ ○
 
 
 
When remaining battery capacity 
is 2 minutes. 
 
Low battery voltage   
signal timing 
 
○ ○ ● ●
 
3 minutes 
● ● ○ ○
 
 
 
When remaining battery capacity 
is 3 minutes. 
Specify the timing for triggering the low 
battery voltage signal. 
5 minutes 
● ○ ○ ○
 
 
5 minutes backup 
20 minutes 
○ ● ○ ○
 
 
 
20 minutes backup 
30
 minutes 
● ● ○ ○
 
 
 
30
 minutes backup 
40
 minutes 
○ ○ ● ○
 
 
 
40
 minutes backup 
60
 minutes 
● ○ ● ○
 
 
 
60
 minutes backup 
90
 minutes
 
○ ● ● ○
 
 
 
90
 minutes backup 
120
 minutes
 
● ● ● ○
 
 
 
120
 minutes backup 
 
Battery backup time 
(RESTART) 
 
● ○ ● ●
 
180
 minutes
 
○ ○ ○ ●
 
 
 
180
 minutes backup 
Set the UPS backup time on power 
outage. 
An external battery must be connected 
for settings of 20 minutes or higher. 
These external battery accommodate by 
Technical Service Personnel.Ask for 
Tehnical Service Personnel. 
Do not use another setting.
 
5 year 
● ○ ○ ○
 
 
5-year lifetime type 
10 year 
○ ● ○ ○
 
 
 
10-year lifetime type 
 
Battery type 
(RESTART) 
 
○ ● ● ●
 
3 year 
● ● ○ ○
 
 
 
3-year lifetime type 
Set the battery type. 
Set this when you exchange the battery 
or connect an external battery. 
180 days 
● ○ ○ ○
 
 
Check batteries every 180 days. 
90 days 
○ ● ○ ○
 
 
 
Check batteries every 90 days. 
30 days 
● ● ○ ○
 
 
 
Check batteries every 30 days. 
 
Battery check schedule 
 
● ● ● ●
 
None 
○ ○ ● ○
 
 
 
No battery check. 
Set the interval (number of days) for the 
automatic battery check. The check is 
carried out automatically when the 
specified number of days has elapsed. 
Do not reset 
● ○ ○ ○
 
 
Do not reset. 
 
 
Reset remaining 
battery life 
 
○ ○ ○ ○
 
Reset 
○ ● ○ ○
 
 
 
Reset the battery information (remaining life, accumulated battery 
operating time, number of power outages, LED remaining life display), 
when you exchange the battery. 
 
LED blinks 
LED off