13. Alarm Sounds 
 
The alarm buzzer emits sound patterns to alert you to failures and error conditions in the 
UPS. Check the sound pattern and refer to the following table to for the steps to take. 
 
 
 
 
 
Sound Pattern 
UPS Status 
What to Do 
This is a mechanical 
failure. 
Contact your supplier. 
During bypass operation 
The bypass breaker is 
tripped.
 
Reset the bypass breaker. 
See §11.7 “Bypass Breaker Reset”.
 
 
 
 
Continuous tone 
 
 
 
 
The battery is exhausted. 
The UPS will restart automatically when 
utility power is restored. 
Power is being supplied 
from the battery because of 
an input voltage or 
frequency error. 
Input the correct voltage or frequency. 
The input breaker   
  MAIN MCCB    was set to 
“OFF” during inverter 
power supply. 
Set the input breaker    MAIN MCCB    to 
“ON”. 
     
 
2 seconds 
 
**
              **            **... 
2 beeps   2 beeps   2 beeps  
 
The UPS is performing a 
battery check. 
Wait for the battery check to end. 
You can stop the battery check by 
pushing
 
  and holding it for   
1 second. 
Continuous beeps 
********
... 
The battery voltage is low. 
Input the correct voltage or frequency. 
Set the input breaker    MAIN MCCB    to 
“ON”. 
1 second 2 seconds 
 
****
                    **** 
****
... 
The load devices connected 
to the output exceed the 
rated capacity. 
Connected fewer load devices to the 
output. 
    2 seconds 
 
*******
    ******* 
7 beeps          7 beeps 
The battery check result 
was an error. 
The battery must be exchanged. 
Contact your supplier. 
The battery has reached 
half of its service life. The 
red BATT.LOW indicator 
lights. 
A battery exchange is recommended. 
Contact your supplier. 
You can press 
 
to stop the buzzer 
sound. 
 
    2 seconds 
 
*****
            *****... 
5 beeps          5 beeps 
The battery has reached its 
service life. 
The red BATT.LOW 
indicator blinks. 
The battery must be exchanged. 
Contact your supplier. 
You can press
 
 
to stop the buzzer 
sound and red BATT.LOW blinking, but 
they will start again the next time the 
UPS is powered on. 
This will continue until you exchange the 
battery. 
 
 
Note : Contact your supplier if any other failure occurs in the UPS. 
 
Press
 
 
to stop the buzzer sound.