− 36 − 
 
15. Functional Description 
 
15.1 Basic Operation 
 
(1) Normal Operation  
In normal operation, the UPS switches automatically
*
 between the three modes (a) to (c) 
depending on the state of the power.   
*
 The UPS does not switch automatically when item ① “UPS operation mode” in 
§
10.1 
“Setup Menu Item List” is set to “Double Conversion”.   
However,The UPS switch automatically according to the state of the input power and the 
load condition when item  ①  "UPS operation mode" in  §10.1 "Setup Menu Item List" is 
set to "Economy". 
 
(a)  Active Filter mode 
The UPS operates in Active Filter mode when the input power voltage is within a 
certain range and the output power factor is below a certain value. In Active Filter 
mode, the UPS receives power from the utility power source and supplies it to the load. 
At the same time, it compensates for high frequencies in the input power at the 
inverter. The batteries are kept continually charged and ready in case a problem 
(outage or voltage drop) occurs in the utility supply. 
 
 
 
 
 
 
 
 
 
 
Power supply route in 
Active Filter
 mode                             
Indications by LEDs 
 
(b)  Double Conversion mode 
The UPS switches to Double Conversion mode when the input power voltage is outside 
a certain range. In Double Conversion mode, the UPS converts AC power from the 
utility power source into DC power through the rectifier, and reconverts this DC power 
back into AC power through the inverter and supplies it to the load. The output power 
is stable AC power synchronized with the input power source. The batteries are kept 
continually charged and ready in case a problem (outage or voltage drop) occurs in the 
utility supply
 
 
 
 
 
 
 
 
 
 
 
 
Power supply route in Double Conversion mode                                  Indications by LEDs 
 
Utility 
power
 
Output
 
Converter
 
Rectifier
 
Inverter
 
Charger
 
Batteries
 
 
Utility 
power 
 
Output 
Converter 
 
Rectifier 
Inverter 
 
Charger
 
Batteries