Sanyo E11A202U User Manual

Page of 47
 
− 40 − 
 
15.4 Specifications 
 
Item  
Standard or Performance 
Notes 
MODEL E11A202U001 
E11A202U001J 
(*6) 
Output capacity 
2.0kVA/1.4kW 
 
Cooling system 
Forced air cooling 
 
Type of Input pulg 
NEMA 5-20P 
NEMA L5-30P 
(*6) When the plug is NEMA_5-20, the 
input and output voltage of UPS are 
120V. only (For UL rules.) 
Phases 
Single phase, 2-wire 
 
120V 100,110,115,120V 
 
Voltage 
-20% to +15% Double Conversion mode 
±5% Economy /Active Filter mode 
±10% Fixed Economy mode 
User settable   
(Rated voltage same as output voltage) 
Frequency 
50Hz or 60Hz 
±10%: Double Conversion mode 
±1, 3, 5%: Economy /Active Filter mode 
Power requirements 
1.8kVA 
Max. capacity during battery charging 
AC in
pu
Input power factor 
0.95 or more 
During rated output                            (*2) 
Type of receptacle 
NEMA 5-20R×4 NEMA 
L5-30R×1 
 
Phases 
Single phase, 2-wire 
 
Voltage 
120V 
100, 110, 115, 120V  (*6) User settable 
Voltage regulation 
Rated voltage 
±2% 
 
Rated frequency 
50Hz or 60Hz 
Same as input frequency   
(auto selection) 
Frequency regulation 
Rated frequency 
±0.5% Double Conversion mode 
Rated frequency 
±1, 3, 5% Economy/Active Filter 
 mode 
1, 3, 5% selectable 
Internal oscillator accuracy 
±0.5%  
Voltage waveform 
Sine wave 
 
Distortion factor of voltage 
waveform 
Linear load: 3% or less 
100% rectifier load: 7% or less 
During rated output 
Rapid load 
change 
 
0% 
⇔ 100% at transient or output 
switch 
Power outage, 
recovery 
 
Rated voltage 
±5 % 
During rated output 
Transient 
voltage 
variation 
Rapid input 
voltage change 
 
±10% variation 
Response time 
5 cycles or less 
 
Load power factor (lag) 
0.7 (lag) 
Variation range 0.7 (lag) to 1.0 
Overcurrent protection 
Auto switch to bypass circuit at 105% or more  With auto return function 
Inverter 105% 
200ms 
AC Ou
tpu
Overload 
capability 
Bypass 20A 
or 
more 
 
Type 
Small sealed lead battery 
 
Rated capacity 
10 A・h 
20 hour ratio 
Number 
4 (12V per battery) 
4 in direct series 
Batte
rie
Backup time 
5 minutes 
At 25°C (77°F) ambient temperature, 
rated load 
Generated heat 
250W 
During Double Conversion mode 
Input leakage current 
3mA or less 
 
Operating environment 
Ambient temperature: 0 to 40°C (32 to 104°F) 
Relative humidity: 20 to 90% 
(*3) 
Acoustic noise 
45 dB or less 
1 m (approx. 40 inches) from UPS front 
panel, 'A' characteristics (linear load) 
Safety standard 
UL1778-4th/C22.2 No.107.3-05-2nd:2005 
 
EMI standard 
FCC Part 15,Sub partB,Class-A 
And EN55022 Class-A 
Other quotation standards 
EN62040-1-1:2003 (For LVD) 
EN50091-2:1995 (For EMC) 
EN55024:1998/A1:2001/A2:2003 (For EMC) 
EN55022:1994/A1:1995/A2:1997 (For EMC) 
 
(*1): The inverter is capable of operation synchronized with AC input and instantaneous switchover 
provided that the AC input frequency is within 
±3% (or 1%, 3%, 5%, selectable) of the rated 
frequency, and the AC input voltage is within +15% to-20% of the rated voltage. 
The UPS enters battery operation with the AC input frequency is outside the specified range. 
(*2):  When input voltage waveform distortion is under 1%.   
(*3):  The UPS contains batteries. Battery service life will be foreshortened if the UPS is used in an 
environment where the ambient temperature exceeds 30°C (86°F).   
(*4): If grounded, the ground phase of the input and output must match according to UPS specifications. 