Sanyo E11A202U User Manual

Page of 47
 
− 39 − 
 
15.3 Protective Function Table 
The following table shows functions and operations which activate to protect the UPS. 
The  ○  mark indicates lit LEDs and buzzer alarms. 
 
Operation panel (front panel) indicators 
Alarms 
Item 
INPUT 
Green 
OUTPUT 
Green 
INV.ON 
STAND 
BY 
Green 
ALARM 
Red 
O.L 
Red 
BATT. 
LOW 
Red 
Buzzer 
pattern 
(*1) 
Protective 
functions 
(UPS operations) 
Notes 
Preparation 
 (*2) (*2) - 
 
 
 
Rectifier, charger, 
operation 
Power up 
Normal 
 
 
 
 
 
 
 
Inverter, charger 
operation 
Power up, 
operation 
Serious 
failure 
 
 
Blink 
 
Blink 
 
 
 
 
(1) 
Stop inverter   
Bypass supply 
 
Overload 
(effective 
value) 
 
 
Blink 
 
Blink 
 
 
 
 
(4) 
Auto return 
Forced 
bypass 
 
 
Blink 
 
Blink 
 
 
 
 
Bypass supply 
Charger operation 
Manual switch 
to bypass supply 
Input over 
voltage 
 
Blink 
 
 
 
 
 
 
(2) 
Battery 
operation 
Input over 
voltage 
(prolonged) 
 
Blink 
 
 
 
 
 
 
(3) 
Battery 
operation (*3) 
Power 
outage 
 
Blink 
 
 
 
 
 
 
(2) 
Battery 
operation 
Power 
outage 
(prolonged) 
 
Blink 
 
 
 
 
 
 
(3) 
Battery 
operation (*3) 
Input error 
(frequency) 
 
Blink 
 
 
 
 
 
 
(2) 
Battery 
operation 
Input error 
(prolonged) 
 
Blink 
 
 
 
 
 
 
(3) 
Stop rectifier and 
charger 
 
 
Continue inverter 
supply. 
 
Battery 
operation (*3) 
Battery 
failure 
 
 
Blink 
 
Blink 
 
 
 
 
(1) 
Stop inverter 
Bypass supply 
 
 
(*1): Press 
  on the front panel of the UPS to stop the buzzer. If a failure occurs, contact 
your supplier or Sanyo Denki representative as soon as possible. 
  Buzzer sound patterns: 
   (1) * 
Continuous tone 
   (2) **......**...... 
   (3) **********......  Continuous beeps 
   (4) ****......****... 
 
(*2): In this state, the LED blinks or is off, depending on the setting of item  ⑪ “Inverter stop 
operation”" in §10.1 “Setup Menu Item List”. 
 When 
item 
  is set to “Bypass”:  ○ Blinks 
 When 
item 
  is set to “OFF”:  - 
 
(*3): Battery operation. Stops inverter operation when final battery discharge is reached.