Sanyo E11A202U User Manual

Page of 47
 
− 38 − 
 
15.2 Protective Functions 
 
(1) Overload Protection 
If the UPS output is overloaded by exceeding the current capacity of the inverter, such as 
when a computer system boots up, the output selector switch automatically switches the 
source of AC power from the inverter to the bypass circuit, without interruption. After a 
certain period of time has elapsed, the source of power to the load is switched back to the 
inverter without interruption (auto-return), as shown in §15.1(1). 
 
Note: When item  ⑩ “Overload recovery operation” in §10.1 “Setup Menu Item List” is set 
to “Bypass”, the UPS switches to inverter power supply without interruption when 
the overload is resolved. 
 
 
 
 
 
 
 
 
 
 
 
Power supply route on failure of utility power             Indications by LEDs 
 
(2) Inverter Fault Protection 
If a fault occurs in the inverter, the output selector switch activates automatically and 
switches from inverter power to bypass power without interruption. The red ALARM 
indicator lights, and the alarm buzzer sounds. The power supply route is the same as for 
an overload. Press 
  to stop the buzzer.   
 
 
 
 
 
 
 
 
 
 
 
LED indications when an inverter fault occurs 
 
Note: What to do if an inverter fault occurs   
Output from the UPS will stop if a power outage occurs during bypass operation due 
to an inverter fault. Contact your supplier or a Sanyo Denki representative as soon 
as possible.
 
 
 
Utility 
power 
 
 
 
 
Output
 
Converter
 
Inverter
 
Charger 
 
Batteries 
 
Rectifier