Schneider Electric 230 VAC User Manual

Page of 20
Smart-UPS 750-3000 VA 120/208/230 Vac Rack-mount
10
Network Management Card Settings 
These settings are available only on units that have a Network Management Card (NMC) and are set in 
the factory. These settings can only be modified using an external interface, like the NMC web interface.
•  NMC IP Address Mode
•  NMC IP Address
•  NMC Subnet Mask
•  NMC Default Gateway
Function
Factory Default Options
Description
Name String 
Outlet Group
Outlet Group 1
Edit these names using an external interface, such as the Network 
Management Card Web interface.
UPS Name String UPS Outlets
Turn On Delay
0 sec
Set the value in 
seconds
The amount of time the UPS or Switched Outlet 
Group will wait between receiving the command 
to turn on and the actual startup.
Turn Off Delay
• 0  sec  (UPS 
Outlets)
• 90 sec (Switched 
Outlet Groups)
Set the value in 
seconds
The amount of time that the UPS or Switched 
Outlet Group will wait between receiving the 
command to turn off and the actual shut down.
Reboot Duration 8 sec
Set the value in 
seconds
The amount of time that the UPS or Switched 
Outlet Group must remain off before it will 
restart.
Minimum Return 
Time
0 sec
Set the value in 
seconds
The amount of battery runtime that must be 
available before the UPS or Switched Outlet 
Group will turn on.
Load Shed On 
Battery
Disabled
• Shutdown with 
Delay
• Shutdown 
immediately
• Turn off 
immediately
• Turn off with delay
• Disabled
When the unit switches to battery power, the UPS 
can disconnect power to the Switched Outlet 
Group to save runtime.
Configure this delay time, use the
 L
OAD
 S
HED
 
T
IME
 
WHEN
 O
N
 B
ATTERY
 setting.
Load Shed Time 
when On Battery
Disabled
Set the value in 
seconds
The amount of time the outlets will function on 
battery power before they will turn off.
Load Shed On 
Runtime
Disabled
• Shutdown with 
delay
• Shutdown 
immediately
• Turn off 
immediately
• Turn off with delay
• Disabled
When the battery runtime falls below the 
specified value, the Switched Outlet Group will 
turn off.
Configure this time using the 
L
OAD
 S
HED
 
R
UNTIME
 R
EMAINING
 setting.
Load Shed On 
Runtime 
Remaining
Disabled
Set the value in 
seconds
When the remaining runtime reaches this level, 
the Switched Outlet Group will turn off.
Load Shed on 
Overload
Disabled
• Disabled
• Enabled
In the event of an overload (greater than 100% 
output), the Switched Outlet Group will 
immediately turn off to conserve power for 
critical loads. The Switched Outlet Group will 
only turn on again with a manual command.