3. LED Lights and Audible Alarm Safeties
At startup, a 5-second delay occurs while the control board conducts an internal timer 
check. A beep occurs when power is turned off. The red LED indicates proper control 
voltage and remains on unless a control voltage problem occurs. The green LEDs 1 
through 4 energize and sequence from startup as listed in the table below. Note that 
the order of the LEDs from the outer edge of the control board is 1, 4, 3, 2. For more 
information, see "II.B. Sequence of Operation."
Sequence Step
LED
Energized
Time LEDs are On 
Min.
Max.
Avg.
1-Minute Fill Cycle 4
WV
1 minute
Harvest Cycle
1, 4, 2
Comp, FMR, 
WV, HGV
2 minutes 20 minutes 3 to 5 minutes
Freeze Cycle
1
Comp, FMR, 
PM, LLV
5 minutes freeze timer
setting
30 to 35 minutes
Pump-Out Cycle
1, 4*, 3, 2
Comp, FMR, 
WV*, PM, 
HGV
10 seconds 20 seconds *pump-out timer 
setting
The built in safeties shut down the unit and have alarms as listed below.
No. of Beeps 
(every 3 sec.)
Type of Alarm
Notes
1
High Evaporator Temp.  
(temperature > 127°F)
                         (53°C)
Check for harvest problem (stuck HGV or 
relay), hot water entering unit, stuck HM, or 
shorted thermistor. 
2
Harvest Backup Timer 
(harvest > 20 min. for 
two cycles in a row)
Orange "H TIMER" LED on. 
Check for open thermistor, HGV not opening, 
TXV or LLV leaking by, WRV leaking by, low 
charge, or inefficient Comp.
3
Freeze Timer 
(freeze > freeze timer 
setting for two cycles in a 
row) 
Timer is factory set using 
S4 dip switch 9 & 10
Yellow "F TIMER" LED on. 
Check for F/S stuck closed (up), WV leaking 
by, HGV leaking by, PM not pumping, TXV not 
feeding properly, LLV not opening, low charge, 
HM not bypassing, or inefficient Comp.
To reset the above safeties, press the "ALARM RESET" button with the power supply on.
6
Low Voltage 
(92VAC±5% or less)
Red LED turns off if voltage protection 
operates.  
The control voltage safeties automatically reset 
when voltage is corrected.
7
High Voltage 
(147VAC±5% or more)
Legend: 
Comp–compressor; FMR–fan motor-remote; F/S–float switch; HGV–hot gas 
valve; 
HM–headmaster (C.P.R.); LLV–liquid line valve; PM–pump motor;   
TXV–thermostatic expansion valve; WRV–water regulating valve; WV–inlet 
water valve