Mitsubishi Electronics MR-J3-T User Manual

Page of 52
Timing chart:
You must turn the power off and on again to activate this parameter.
Home Position Return
Positioning with Digital Inputs
4 - 16
MITSUBISHI ELECTRIC
Fig. 4-5:
Home position return sequence in dogless Z-phase reference mode
PC04 “Home pos. return speed”
PC06 “Home offset”
PC05 “Creep speed”
Auto/Manual mode (MD0)
ON
OFF
Select point table no. (DI0)
Start command
Forward (ST1)
ON
OFF
Start command
Reverse (ST2)
ON
OFF
Servo motor speed setting
Z-phase of encoder
ON
OFF
Home  return complete (ZP)
ON
OFF
No.
Code
Function
Description
PA05
*FTY
Feed length multi-
plication factor
Needed here to scale the home position value to the physical coor-
dinate system.
PC02
*ZTY
Home position re-
turn mode
Selects the home position return mode:
A: Dogless Z-phase reference mode
PC03
*ZDIR
Home position re-
turn direction
0: Incrementing counting of encoder pulses
1: Decrementing counting of encoder pulses
PC04
ZRF
Home position re-
turn speed
Sets home position return speed until first detection of the Z-phase
in [rpm].
PC05
CRF
Creep speed
Speed for precise movement to home position in [rpm].
PC06
ZST
Home position off-
set (shift)
Distance between the encoder zero point (Z-phase) and the physi-
cal home position in [µm].
PC07
*ZPS
Home position re-
turn position value
The home position return stops when the Z-phase position is
reached.You can enter a non-zero coordinate for this position [in
10
STM
µm] with this parameter.
Table 4-1: Parameter reference table