Class 8839 58M Enclosed AC Drives
Specifications
183
09/2003
©
 2000–2003 Schneider Electric All Rights Reserved
PART 3 EXECUTION
3.01 INSPECTION
a. Verify that the location is ready to receive work 
and the dimensions are as indicated.
a. Do not install AC Drive equipment until the 
building environment can be maintained within 
the service conditions required by the 
manufacturer.
3.02 PROTECTION
a. Before and during the installation, the AC 
Drive equipment shall be protected from site 
contaminants and debris.
3.03 INSTALLATION
a. Installation shall comply with manufacturer's 
instructions, drawings and recommendations.
b. The AC Drive manufacturer shall provide a 
factory certified technical representative to 
supervise the contractor's installation, testing 
and start-up of the AC Drive(s) furnished 
under this specification for a maximum total of 
[1,2,3] days. The start-up service shall be 
quoted as a separate line item.
3.04 TRAINING
a. An on-site training course of [1,2] training days 
shall be provided by a representative of the AC 
Drive manufacturer plant and/or maintenance 
personnel and quoted as a separate line item.
END OF SECTION