FIGURE 28.
IMPORTANT
THE INSTALLATION OF SAFETY FLOW SWITCH AS SHOWN IS REQUIRED TO PROTECT THE BOILER IN CASE OF WATER SERVICE 
INTERRUPTION OR CIRCULATOR  FAILURE.
+   PIPING AND FITTINGS BETWEEN GATE VALVES AND BOILERS SHOULD BE BRASS OR BRONZE. OTHER PIPING SHOULD 
CONFORM TO LOCAL CODES.
GATE VALVES ARE SHOWN FOR SERVICING BOILER. HOWEVER, LOCAL CODES SHALL GOVERN THEIR USAGE.
*  
PRESSURE RELIEF VALVE RATING SHOULD NOT EXCEED PRESSURE CAPACITY OF ANY COMPONENT IN THE SYSTEM.
**  INSTALL THERMOMETER AND PRESSURE RELIEF IN OPENINGS PROVIDED ON HW-520, HW-610 & HW-670.
WIRING - FIGURES 16 and 17 on 
pages 24 and 25.
INSTALL IN ACCORDANCE
WITH ALL LOCAL CODES
ONE HW-300, HW-399, HW-420, HW-520, HW-610 OR ONE HW-670 UP-FLOW MODEL
COMMERCIAL BOILER WITH VERTICAL TANK
USE THIS TABLE FOR CORRECT
PUMP AND WATER PIPE SIZE
Model
Number
Minimum
Pipe Size
(Inches)
B & G
Pump
Size
*Armstrong
Pump Size
HW-300
1-1/4"
125
S-25 1-1/4"
HW-399
1-1/2"
1-1/2" HV
H-32 1-1/2"
HW-420
1-1/2"
1-1/2" HV
H-32 1-1/2"
HW-520
1-1/2"
1-1/2" HV
H-32 1-1/2"
HW-610/670
2"
2"
S-35
* Assumes 50 equivalent feet of piping or less.
 
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE 
TEMPERATURE AT FIXTURES. SEE TANK TEMPERATURE 
CONTROL  WARNING  ON  PAGE  11.  IF  HIGHER  PREHEAT 
TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE 
BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT 
WATER SUPPLIED TO FIXTURES.
PIPING