TWO HW-399's, HW-420's, HW-520's, HW-610's or HW-670's UP-FLOW MODEL
COMMERCIAL BOILER WITH VERTICAL TANK, CER-TEMP 80
IMPORTANT
THE  INSTALLATION  OF  SAFETY  FLOW  SWITCH AS  SHOWN  IS 
REQUIRED TO PROTECT THE BOILER IN CASE OF WATER SERVICE 
INTERRUPTION OR CIRCULATOR  FAILURE.
+   PIPING AND FITTINGS BETWEEN GATE VALVES AND BOILERS 
SHOULD  BE  BRASS  OR  BRONZE.  OTHER  PIPING  SHOULD 
CONFORM TO LOCAL CODES.
GATE VALVES ARE SHOWN FOR SERVICING BOILER. HOWEVER, 
LOCAL CODES SHALL GOVERN THEIR USAGE.
*   PRESSURE  RELIEF  VALVE  RATING  SHOULD  NOT  EXCEED 
PRESSURE CAPACITY OF ANY COMPONENT IN THE SYSTEM. 
**  INSTALL THERMOMETER AND PRESSURE RELIEF IN OPENINGS 
PROVIDED ON HW-520, HW-610 & HW-670.
WIRING - FIGURES 21 to 27 on 
pages 28 to 32.
HEATERS SPACED 30" APART
INSTALL IN ACCORDANCE
WITH ALL LOCAL CODES
FIGURE 30.
 
DANGER
TEMPERATURE  SETTING  SHOULD  NOT  EXCEED  SAFE  USE  TEMPERATURE 
AT FIXTURES. SEE TANK TEMPERATURE CONTROL WARNING ON PAGE 11. IF 
HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE 
BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WATER SUPPLIED 
TO FIXTURES.
USE THIS TABLE FOR CORRECT
PUMP AND WATER PIPE SIZE
Model
Number
Minimum
Pipe Size
(Inches)
B & G
Pump
Size
*Armstrong
Pump Size
A
B
HW-300
2"
1-1/2"
2"
S-35
HW-399
2"
1-1/2"
2"
S-35
HW-420
2"
1-1/2"
2"
S-35
HW-520
2"
1-1/2"
2"
S-35
HW-610/670
2-1/2"
1-1/2"
2-1/2"
S-45 2-1/2"
* Assumes 50 equivalent feet of piping or less.