FIGURE 29.
ONE HW-300, HW-399, HW-420, HW-520, HW-610 OR ONE HW-670  UP-FLOW MODEL
COMMERCIAL BOILER WITH HORIZONTAL TANK
WIRING - FIGURES 16 and 17 on 
pages 24 and 25.
INSTALL IN ACCORDANCE
WITH ALL LOCAL CODES
IMPORTANT
THE INSTALLATION OF SAFETY FLOW SWITCH AS SHOWN 
IS REQUIRED TO PROTECT THE BOILER IN CASE OF WATER 
SERVICE INTERRUPTION OR CIRCULATOR  FAILURE.
+   PIPING AND  FITTINGS  BETWEEN  GATE  VALVES AND 
BOILERS  SHOULD  BE  BRASS  OR  BRONZE.  OTHER 
PIPING SHOULD CONFORM TO LOCAL CODES.
GATE  VALVES  ARE  SHOWN  FOR  SERVICING  BOILER. 
HOWEVER, LOCAL CODES SHALL GOVERN THEIR USAGE.
*   PRESSURE  RELIEF  VALVE  RATING  SHOULD  NOT 
EXCEED  PRESSURE  CAPACITY  OF ANY  COMPONENT 
IN THE SYSTEM.
**  INSTALL  THERMOMETER AND  PRESSURE  RELIEF  IN 
OPENINGS PROVIDED ON HW-520, HW-610 & HW-670.
 
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE 
TEMPERATURE AT FIXTURES. SEE TANK TEMPERATURE 
CONTROL  WARNING  ON  PAGE  11.  IF  HIGHER  PREHEAT 
TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE 
BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT 
WATER SUPPLIED TO FIXTURES.
USE THIS TABLE FOR CORRECT
PUMP AND WATER PIPE SIZE
Model
Number
Minimum
Pipe Size
(Inches)
B & G
Pump
Size
*Armstrong
Pump Size
HW-300
1-1/4"
125
S-25 1-1/4"
HW-399
1-1/2"
1-1/2" HV
H-32 1-1/2"
HW-420
1-1/2"
1-1/2" HV
H-32 1-1/2"
HW-520
1-1/2"
1-1/2" HV
H-32 1-1/2"
HW-610/670
2"
2"
S-35
* Assumes 50 equivalent feet of piping or less.