Bosch FMR-1000-RCMD User Manual

Page of 44
16
en | Specifications
Remote Command Center
F.01U.078.098 | 3.0 | 2011.11
Installation and Operation Guide
Bosch Security Systems, Inc.
11.1.1
Wiring Specification
11.2
Mechanics
11.3
Environmental Conditions
11.4
Trademarks
Phillips is a registered trademark of the Phillips Screw Co.
Current consumption at 24 V DC/FWR
Standby current
30 mA maximum (only Power LED on)
Alarm current
120 mA maximum (with annunciator lit and piezo 
on)
Cable entries
3 knockouts for 1/2 in. diameter conduit 
connectors in the back, bottom and top side
Connections
2 connectors (4 terminals)
Wire gauge
AWG 12 to 18 (diameter 3.25 mm
2
 to 0.75 mm
2
)
Wire type
Non-shielded, four conductor wire
Maximum number of annunciators per 
system 
8 (FMR-1000-RA and/or FMR-1000-RCMD)
Distance allowed between FACP and 
annunciator
2000 ft (610 m)
Maximum length of Option Bus wiring
4000 ft (1219 m), depending on cable gauge and 
connected devices
Operating and display elements
6 LEDs
Fire (red), Gas Alarm (blue), Power (green), 
Supervisory, Silenced and Trouble (3 x yellow)
LCD
4 line x 20 character LCD display, backlit
Keys
Keys for Drill, Reset, Silenced, Acknowledge [ACK], 
4 arrow keys
Piezo
Built-in piezo sounder
Mounting holes back box
2, spaced 5.5 in. (140 mm) apart
Housing material
ABS-FR
Color
Red
Dimensions (W x H x D) 
FMR-1000-RCMD
7.40 x 4.41 x 2.40 in. (188 x 112 x 61 mm)
Back box
7.40 x 4.41 x 1.89 in. (188 x 112 x 48 mm)
Weight
19.4 oz (550 g)
Environment
Indoor, dry
Operating temperature
32 °F to 120 °F (0 °C to +49 °C)
Storage temperature
-4 °F to 140 °F (-20 °C to +60 °C)
Relative humidity
Up to 95%, non-condensing
Protection class per IEC 605029
IP 30