Vulcan-Hart BVD36FP52(F,L)N-1 User Manual

Page of 40
Page 22
19400-3-0406
BURNER ORIFICE CONVERSION - Slope style burners
8b.  On  model  BVP42FP3  series  fireplaces,  you  will  have  a 
rectangular slope style burner. To gain access to the main 
orifice, disconnect the gas supply tubing at the air shutter.
9b.  Remove the orifice holder from the air shutter, then remove 
the NG orifice.
10b. Replace  the  removed  NG  orifice  with  the  new  LP  orifice 
designated in the orifice reference chart for your fireplace 
model. Secure the new orifice and replace the orifice/orifice 
holder back into the air shutter and secure.
11b. Loosen the air shutter screw and reset the air shutter opening 
in accordance with the dimension shown in the reference chart 
for the appropriate model fireplace.
PILOT ORIFICE CONVERSION
12.  Locate the pilot assembly.
13.  Pull upward on the round pilot flame hood to remove.
14.  Using a 5/32" Hex Allen wrench, remove the pilot orifice, 
then replace with the new pilot orifice marked #35.
IMPORTANT:  Failure to install the correct orifice will result 
in unit over-firing that could overheat the appliance and result 
in a fire.
15.  Refer to log placement found in your fireplace installation 
manual to place logs onto the burner assembly.
16.  Loosen screw and attach a manometer or pressure gauge to 
the outlet pressure tap of the control valve.
17.  Turn on the gas supply. Turn on the electrical supply to the 
appliance. Check for gas leaks using a soap and water solution 
or leak detection solution. Bubbles indicate a leak that MUST 
be corrected. Do not use an open flame to test for gas leaks.
18.  Check  the  air  shutter  opening.  See  chart  and  illustration 
below.
19.  Relight the main burners and verify proper burner ignition 
and operation.
20.  With  the  main  burner  burning,  read  the  pressure  on  the 
manometer or pressure gauge. The pressure on the gauge 
should read between 9.8" and 10.2"w.c.
21.  Turn off the gas supply. Turn off the electrical supply to the 
appliance.
22.  Remove the manometer or pressure gage. Tighten the screw 
in the pressure tap.
23.  Turn on the gas supply. Turn on the electrical supply to the 
appliance.
24.  Immediately test all gas line connections and the control valve 
for gas leaks using a soap and water solution or gas detection 
for solution. Bubbles indicate a leak that MUST be corrected. 
Do not use an open flame to check for gas leaks.
25.  Using a ball point pen, fill out the conversion label that is 
supplied with the conversion kit. Place the conversion label 
adjacent to the rating plate.
26.  Test operation of fireplace once again. Allow the fireplace to 
operate for at least 10 minutes and check flame coloration. 
Flame  on  rear  of  burner  should  be  yellow  without  any 
orange-colored tip. Minor adjustment of the air shutter may 
be necessary to "tune in" the proper flame color.
The burner flame and pilot flame must be checked for proper 
flame characteristics, as outlined in this manual. 
V E R I F Y I N G   I N P U T  R AT E   O F  C O N V E RT E D 
FIREPLACE
The input of the fireplace must be checked as follows:
1.  Turn off all other gas appliances. Clock the gas meter and 
determine the number of seconds required to consume one 
cubic foot of gas.
2.  3600 ÷ time (in seconds) = cu. ft. per hour.
3.  Then cu. ft. per hour x heating value of gas = input rate 
 
(BTU/Hr). On installation without gas meters, check manifold 
for proper pressure.
Note:  The rate noted on the data plate is measured after 45 minutes 
of continuous operation and adjusted for test conditions 
such as temperature, and barometric pressure. The above 
procedure is a check for correct conversion only.
PLACEMENT OF GAS CONVERSION LABEL
Conversion label 2139 is to be filled out completely and placed 
with the data plate attached near the valve.
If the appliance has not been installed, or a warranty card has not 
been returned to Empire Comfort Systems, Inc., check off type of 
gas converted to on card (for reference once the unit is installed). 
Also, indicate conversion by adding "Conv." behind gas.
MODEL
AIR SHUTTER 
SETTINGS
BURNER 
ORIFICE
Opening "A"
Propane/LP
BVD34
5/16"
(7.9mm)
1.35mm
P-289
BVD36
5/16"
(7.9mm)
1.45mm
P-208
BVP42
FULL OPEN
1.65mm
P-250
Air  shutter  settings  shown  are  factory  settings.  Some  venting 
configurations  may  require  minor  air  shutter  adjustments  for 
optimum performance.
“A”