Quantum atl 7100 Installation Instruction

Page of 68
Chapter 1  Library Specifications and Site Requirements
Site Requirements
8
Quantum|ATL 7100 Series Facilities Planning and Installation Guide
Table 4   Library Floor 
Space Requirements
Floor Leveling
1
The floor must be level to within 1/4” over a 6' x 6' area.
Floor Loading
1
A standard raised computer floor rated at 250 lb./ft
2
 is sufficient to 
support a fully loaded library.
Floor Clearance
1
The cabinet has a nominal floor clearance of 0.75" (1.9cm).
Power
1
The library’s auto-ranging motor and logic power supplies will 
accept single phase, 90-264VAC input power at 47-63 Hz.
36.5”
24”
Library
(Ramp side/off-load area)
(For maintenance only)
(For maintenance only)
(M
aint
enanc
e ar
ea)
25”
25”
96”
25”
157.5”
74”
Front of library
V
ent
ilat
ion and
c
abli
n
g