Rack Mounting the Switch
3-6
Hardware Installation
Rack Mounting the Switch 
To install the switch in a 19‐inch rack, you need: 
Two rackmount brackets and mounting screws (rackmount kit) shipped with the 
switch.
Four user‐supplied screws to attach the switch to a standard 19‐inch rack.
Refer to 
” on page A‐4 for recommended torque values by screw size.
Guidelines for Rackmount Installation
The installation site must be within reach of the network cabling and meet the 
requirements listed below:
Appropriate grounded power receptacles must be located within 152 cm (5 ft) of the 
location.
A temperature of between 0°C (32°F) and 40°C (104°F) must be maintained at the 
installation site with fluctuations of less than 10°C (18°F) per hour.
Attaching Brackets and Installing in Rack
Proceed as follows to install the switch into a 19‐inch rack:
1.
Attach the rackmount brackets to the switch, as shown in 
, using the eight 
M3x6 mm flathead screws shipped with the switch. Refer to “
A‐4 for recommended torque values by screw size.
Note: To ensure proper ventilation and prevent overheating, leave a minimum clearance 
space of 5.1 cm (2.0 in.) at the left, right, and rear of the switch.
Warning: Before rack-mounting the switch, ensure that the rack can support it without 
compromising stability. Otherwise, personal injury and/or equipment damage may result.
Advertencia: Antes de montar el equipo en el rack, asegurarse que el rack puede 
soportar su peso sin comprometer su propia estabilidad, de otra forma, daño personal o 
del equipo puede ocurrir.
Warnhinweis: Überzeugen Sie sich vor dem Einbau des Gerätes in das Rack von dessen 
Stabilität, ansonsten könnten Personenschäden oder Schäden am Gerät die Folge sein.