Cisco Cisco Unified MeetingPlace Audio Server Maintenance Manual

Page of 349
3-2
Cisco MeetingPlace Audio Server 5.2 Customer Engineering Guide (for Cisco MeetingPlace 8112)
OL-
Chapter 3      Installing the 8112 Server
  Evaluating the site
Warning
Use caution when installing or modifying telephone lines.
Warning
Supplemental earth grounding is required at all times.
Tools used during installation
Refer to 
 for a list of tools needed for installation.
Evaluating the site
Before installing the 8112 server, make sure the MeetingPlace System Manager has provided the name 
of a site contact who can answer relevant questions regarding the site.
Warning
If any of the requirements in this section have not been met prior to installation, do not proceed with 
the installation.
Environmental requirements
The recommended operating temperature range for MeetingPlace is 50-104 degrees Fahrenheit (10-40 
degrees Celsius), with a non-condensing humidity of 5-80 percent.
It is essential to keep the server equipment properly cooled. To ensure this, the 8112 server has three 
internal DC powered fans cool the server. To ensure all system components are adequately cooled, the 
system must meet these requirements:
at least 24 inches (60 cm) of clearance exists in the back of the 8112 server
at least 1.75 inches (4.4 cm) of clearance exists on top of the 8112 server
all module slots must be filled or covered (use filler panels in empty slots)
air flow in an open frame rack must be from front to back
air flow in an enclosed cabinet must be from front to back, bottom to top
Power requirements
Power for the rack system must come from a totally dedicated circuit breaker within 8 feet (2.43 meters) 
of the equipment. Do not plug any other electrical devices into an outlet connected to the circuit breaker 
serving the rack equipment. In addition, the site should have additional power outlets for test and 
maintenance equipment.
MeetingPlace power requirements are 100-115/200-230V, 6/3A, 50/60 Hz. If the power in your area is 
susceptible to fluctuations or interruptions, consider installing surge suppressors or connecting the 
servers to an Uninterruptible Power Supply (UPS). MeetingPlace does not maintain telephony 
connections should the system lose power.
MeetingPlace draws a maximum of 600 watts of power and produces a maximum of 2048 BTU/hour.