Chapter 3      Installing the 8112 Server
  Evaluating the site
T1 digital trunk requirements
T1 Smart Blades support digital connections to a PBX system or to a PSTN. The framing for the digital 
lines can be either extended superframe (ESF) or D4. The digital lines can use either B8ZS coding or 
jammed bit.
Note
We strongly recommend using ESF framing and B8ZS coding. Using D4 framing or jammed bit coding 
may produce unsatisfactory service.
Warning
Supplemental earth grounding is required at all times. This supplemental grounding consists of a 
grounding cable attached to supplemental ground lugs on the back of the 8112 server chassis and is 
permanently connected to an earth ground point at the other end via an appropriate facilities 
grounding terminal.
Shielded cables must be used, and the shield must be electrically terminated at the back of the 8112 
server. MeetingPlace also supports fractional T1 services and has complete flexibility to activate any or 
all ports on a span.
MeetingPlace can use dialed number information to connect the caller directly to a meeting or to 
determine the MeetingPlace services to which the caller has access.
MeetingPlace can also be configured to support devices where the T1 trunk does not provide any 
signaling and is always offhook. This is used in applications where a clear channel connection is 
required.
Table 3-1
Power Requirements by Country
Country
Clearance
Power
Socket
USA
Canada
24 inches of 
clearance in back 
of server
115 VAC
NEMA 5-15R 
socket-outlet 
installed within 8 
feet of the unit
Hong Kong
European Union
61 cm of 
clearance in back 
of server
240 VAC
BS-1363 
socket-outlet 
installed within 2 
meters of the unit
Japan
61 cm of 
clearance in back 
of server
100 VAC (50Hz 
for East Japan; 60 
Hz for West 
Japan)
NEMA 5-15R 
socket-outlet 
installed within 2 
meters of unit