Telephony and LAN planning  3-3
February 27, 2004
Cisco MeetingPlace Audio Server Installation Planning Guide
WARNING
Supplemental earth grounding is required at all times. This 
supplemental grounding consists of a grounding cable attached to 
supplemental ground lugs on the back of the MeetingPlace server chassis and 
permanently connected to an earth ground point at the other end through an 
appropriate facilities grounding terminal. The ground lugs consist of two 
#10 screws. To attach to these, crimp a #10 ring lug onto the ground 
conductor being used. Additionally, all the power outlets in the vicinity of the 
MeetingPlace system must be of the grounding type and they must be 
properly grounded.
Environmental requirements (8106)
The recommended operating temperature range for MeetingPlace is 50°–
95° F (10°–35° C), with a non-condensing humidity of 5%–80% percent.
It is essential to keep the server equipment properly cooled. To ensure this, the 
8106 server has an internal fan assembly with four fans to cool the server. To 
ensure all system components are adequately cooled, the system must meet 
these requirements:
At least 1.5 inches (3.8 cm) of clearance exists in the front and back of the 
8106 server
At least 0.5 inches (1.25 cm) of clearance exists to the right and left of the 
8106 server
At least 0.5 inches (1.25 cm) of clearance exists on the top and bottom of 
the 8106 server
All module slots must be filled or covered (use filler panels in empty slots)
Air flow in an open frame rack or in an enclosed cabinet must be from left 
to right
WARNING
Supplemental earth grounding is required at all times. This 
supplemental grounding consists of a grounding cable attached to 
supplemental ground lugs on the back of the MeetingPlace server chassis and 
permanently connected to an earth ground point at the other end through an 
appropriate facilities grounding terminal. The ground lugs consist of two 
#10 screws. To attach to these, crimp a #10 ring lug onto the ground 
conductor being used. Additionally, all the power outlets in the vicinity of the 
MeetingPlace system must be of the grounding type and they must be 
properly grounded.
Power requirements (8112)
Power for the rack system must come from a totally dedicated circuit breaker 
within 8 feet (2 meters) of the equipment. Do not plug any other electrical 
device into an outlet connected to the circuit breaker serving the rack 
equipment. In addition, the site cannot have additional power outlets for test 
and maintenance equipment.