Ramp Incline Tolerances
The ramp incline tolerances for moving the Cisco CRS 4-slot LCC are as follows:
• 1:12 or 1 inch of rise per 12 inches (30.5 cm) of run (1:6 for existing ramps).
• Maximum rise for any run is 30 inches (76 cm).
• Maximum ramp angle is 10°.
Exception: A ramp with a slope no greater than 1:6 for a run not to exceed 2 feet (61 cm).
Verifying the Installation Floor Plan
The floor plan for the Cisco CRS 4-slot LCC must include enough space to install the chassis in the equipment rack and allow sufficient
airflow for the system. The floor plan must also provide enough room to access chassis components for maintenance (for example,
to remove fan trays, power modules, cables, and air filters).
The following figure shows a top view of the footprint required for installation (with optional front doors installed).
13