Cisco Cisco ONS 15454 M2 Multiservice Transport Platform (MSTP)

Page of 60
• Critical (CR)
• Use Default
• Inherited
Inherited and Use Default severity levels only appear in alarm profiles. They do not appear when you view alarms, history, or
conditions.
Row Display Options
In the network or node view (single-shelf mode) or shelf view (multishelf mode), the Alarm Profiles window (Alarm Profile Editor
for node view) displays three check boxes at the bottom of the window:
• Only show service-affecting severities—If cleared, the editor shows severities in the format sev1/sev2 where sev1 is a
service-affecting severity and sev2 is not service-affecting. If checked, the editor only shows sev1 alarms.
• Hide reference values—Highlights alarms with non-default severities by clearing alarm cells with default severities.
• Hide identical rows—Hides rows of alarms that contain the same severity for each profile.
Apply Alarm Profiles
In the CTC node view, the Alarm Behavior window displays alarm profiles for the entire node and specific cards. In the card view,
the Alarm Behavior window displays the alarm profiles for the selected card. Alarm profiles form a hierarchy. A node-level alarm
profile applies to all cards in the node except cards that have their own profiles. A card-level alarm profile applies to all ports on the
card.
At the node level, you can apply profile changes on a card-by-card basis or set a profile for the entire node.
External Alarms and Controls
External alarm inputs can be provisioned on the Alarm Interface Controller–International (AIC-I) card for external sensors such as
an open door and flood sensors, temperature sensors, and other environmental conditions. External control outputs on these two cards
allow you to drive external visual or audible devices such as bells and lights. They can control other devices such as generators,
heaters, and fans.
Up to 12 external alarm inputs and four external controls are available with the AIC-I card. If you also provision the alarm extension
panel (AEP), there are 32 inputs and 16 outputs. The AEP is compatible with the ONS 15454 ANSI shelf only. It is not compatible
with the ONS 15454 ETSI shelf.
External Alarms
You can provision each alarm input separately. Provisionable characteristics of external alarm inputs include:
• Alarm Type—List of alarm types.
• Severity—CR, MJ, MN, NA, and NR.
• Virtual Wire—The virtual wire associated with the alarm.
13